{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2510-6JP42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2510-6JP42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2510-6JP42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2510-6JP42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2510-6JP42-0AA0, 1000 A rated current, 4-pole, ETU550 electronic trip unit, 242 kA breaking capacity at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2510-6JP42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 1000 A at 40 °C ambient, with no derating required up to 55 °C — the full 1000 A holds across that band. At 60 °C the rating steps to 955 A, then 885 A at 65 °C, and 815 A at 70 °C, per the published thermal curve. Breaking capacity is specified across five voltage points: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 73.5 kA at 690 V. Maximum power loss is 330 W. Dimensions are 320 mm height, 280 mm width, and 120 mm depth. The 280 mm width is the critical panel cutout dimension — verify against existing busbar or mounting footprint before committing the gland plate layout.","metaTitle":"Siemens 3VA2510-6JP42-0AA0 SENTRON MCCB, 1000A, 4P, ETU550","metaDescription":"Siemens SENTRON 3VA2510-6JP42-0AA0 molded case circuit breaker, 1000A rated current, 4-pole, ETU550 trip unit. Breaking capacity 242kA at 240V. Current production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"280 mm","title":"3VA2510-6JP42-0AA0","Height":"320 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"73.5 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"1 000 A","at 60 °C":"955 A","at 65 °C":"885 A","at 70 °C":"815 A","Depth [In]":"4.72 in","Width [In]":"11.02 in","Height [In]":"12.6 in","description":"circuit breaker 3VA2 IEC frame 1000 breaking capacity class H Icu=85kA @ 415V 4-pole, line protection ETU550, LSI, In=1000A overload protection Ir=400A...1000A short-circuit protection Isd=0.6..10x In, Ii=1.5..10x In N conductor protection adjustable (OFF, up to 100%) nut keeper kit","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"330 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"1 000 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"10 000 A","Adjustable response value current / li min.":"1 500 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"1 000 A","Mechanical Service Life (Operating Cycles) / Typical":"10 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d043a3e994934aa20d7dec936cfcdf32.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645446&mlfb=3VA2510-6JP42-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA2510-6JP42-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is 3VA2510-6JP42-0AA0's listed depth?","answer":"The depth is 120 mm (4.72 in)."},{"question":"What is 3VA2510-6JP42-0AA0's listed width?","answer":"The width is 280 mm (11.02 in)."},{"question":"What compliance documentation does Siemens provide for 3VA2510-6JP42-0AA0?","answer":"As a SENTRON series MCCB, this breaker is designed to meet IEC 60947-2 and UL 489 standards. Specific declarations (RoHS, REACH, CE, UKCA, EAC) are typically included in the manufacturer's documentation package available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2510-6JP42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2510-6JP42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}