{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2563-5MN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2563-5MN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2563-5MN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2563-5MN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 series, IEC frame 1000, motor protection circuit breaker, 3-pole, 630A, breaking capacity class M Icu=55kA @ 415V, ETU350M LSI electronic trip unit, shunt trip 110-127V DC/AC.","salesMarkdown":"## Motor protection breaker with ETU350M LSI trip The Siemens 3VA2563-5MN32-0JL0 is a 3-pole IEC frame 1000 circuit breaker in the 3VA2 series, rated 630 A with a breaking capacity class M achieving Icu=55 kA at 415 V. It is configured for motor protection using the ETU350M electronic trip unit with LSI protection — long-time (Ir), short-time (Isd), and instantaneous (Ii) — giving the commissioning engineer adjustable overload and short-circuit coordination for a 250 A to 630 A motor circuit. ## Trip unit settings and auxiliary wiring Overload protection Ir is adjustable from 250 A to 630 A; short-circuit protection Isd is set 3 to 15 times Ir, and instantaneous Ii is fixed at 15 times In (630 A).","metaTitle":"Siemens 3VA2563-5MN32-0JL0 Circuit Breaker, 630A, 55kA @ 415","metaDescription":"Siemens 3VA2563-5MN32-0JL0 IEC frame 1000 motor protection circuit breaker, 630A, Icu=55kA @ 415V, ETU350M LSI trip unit. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c9fd37fa22cbeb51cb06d5bbec3a94bb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645501&mlfb=3VA2563-5MN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2563-5MN32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2563-5MN32-0JL0?","answer":"The ultimate breaking capacity Icu is 55 kA at 415 V, class M, on the IEC frame 1000."},{"question":"What trip unit and protection functions does this breaker have?","answer":"It uses the ETU350M electronic trip unit with LSI protection: long-time (Ir) adjustable 250 A to 630 A, short-time (Isd) adjustable 3 to 15 x Ir, and instantaneous (Ii) fixed at 15 x In."},{"question":"What auxiliary switches and accessories are included?","answer":"The breaker includes a shunt trip (STL) rated 110-127 V DC/AC, two auxiliary switches HQ, one trip alarm switch HQ, one electrical alarm switch, and a nut keeper kit."},{"question":"How do I get current pricing and availability for 3VA2563-5MN32-0JL0?","answer":"This part is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2563-5MN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2563-5MN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}