{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2563-7MP32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2563-7MP32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2563-7MP32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2563-7MP32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 series, IEC frame 1000, 3-pole MCCB, motor protection ETU550M, LSI, In=630A, Icu=110kA @ 415 V.","salesMarkdown":"The Siemens 3VA2563-7MP32-0AB0 is a 3-pole IEC frame 1000 molded case circuit breaker from the 3VA2 series, built for motor protection with an ETU550M electronic trip unit configured for LSI protection (long-time, short-time, instantaneous). The continuous current rating In is 630 A, with overload protection adjustable from 250 A to 630 A. The short-circuit protection settings are adjustable: Isd from 1.2 to 15 times In, and Ii from 3 to 15 times In, giving you flexibility to coordinate with downstream devices. ## Integration into the panel — busbar connection and auxiliary switches This breaker is designed for busbar connection — it comes with a busbar connection kit as part of the order code, so it's ready to plug into a standard IEC busbar system in a switchboard or MCC. It also includes two auxiliary switches (changeover type, H), which give you status feedback for remote monitoring or interlocking without needing to add separate contact blocks. The 3-pole form factor and frame 1000 footprint match the 3VA2 family mounting pattern, so panel cutouts and busbar spacing are consistent across the range.","metaTitle":"Siemens 3VA2563-7MP32-0AB0 Circuit Breaker, 630A, 110kA @ 41","metaDescription":"Siemens 3VA2563-7MP32-0AB0 IEC frame 1000 MCCB, 3-pole, motor protection ETU550M, LSI, In=630A, Icu=110kA @ 415V. Active lifecycle. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c9fd37fa22cbeb51cb06d5bbec3a94bb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1439235&mlfb=3VA2563-7MP32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2563-7MP32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2563-7MP32-0AB0 and how do I get a price?","answer":"This part is sourced to order through our independent distribution channel. Submit an RFQ and we will confirm availability and current pricing at quote time."},{"question":"What is the breaking capacity Icu of this breaker?","answer":"The Icu is 110 kA at 415 V AC, which is the maximum short-circuit current it can safely interrupt."},{"question":"What trip unit does the 3VA2563-7MP32-0AB0 use?","answer":"It uses an ETU550M electronic trip unit with LSI protection (long-time, short-time, instantaneous), adjustable overload from 250 A to 630 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2563-7MP32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2563-7MP32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}