{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2580-5HL32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2580-5HL32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2580-5HL32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2580-5HL32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2580-5HL32-0CL0, molded case circuit breaker, 3-pole, 800 A, ETU320 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V.","salesMarkdown":"The Siemens SENTRON 3VA2580-5HL32-0CL0 is a 3-pole molded case circuit breaker rated for 800 A continuous current at 40 °C, with an ETU320 electronic trip unit. Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that put it in the high-fault tier for industrial main feeders or large sub-distribution. ## Thermal derating and trip settings The ETU320 release gives you adjustable long-time pickup (Ir) from 320 A to 800 A, short-time pickup (li) from 1200 A to 8000 A, and long-time delay (tr) from 0.5 to 17 seconds. That range covers motor feeders, transformer primaries, and general distribution where you need to ride through inrush without nuisance trips.","metaTitle":"Siemens 3VA2580-5HL32-0CL0 SENTRON MCCB, 800 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2580-5HL32-0CL0 molded case circuit breaker, 800 A rated, 3-pole, ETU320 release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"800 A","at 45 °C":"800 A","at 50 °C":"800 A","at 55 °C":"800 A","at 60 °C":"800 A","at 65 °C":"767 A","at 70 °C":"703 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"135 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"800 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value current / Ir max.":"800 A","Adjustable response value current / li max.":"8 000 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=660296&mlfb=3VA2580-5HL32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2580-5HL32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2580-5HL32-0CL0's listed depth (120 mm) on this component line?","answer":"The depth is 120 mm, with a width of 210 mm and height of 320 mm. The 210 mm width is the key dimension for panel cutout planning."},{"question":"What compliance documentation does this brand provide for 3VA2580-5HL32-0CL0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON MCCB, it carries the expected industrial certifications (UL, IEC, CSA, CE) for the class. Specific RoHS and REACH declarations are available from the manufacturer's documentation portal for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2580-5HL32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2580-5HL32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}