{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2580-5KQ32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2580-5KQ32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2580-5KQ32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2580-5KQ32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2580-5KQ32-0HH0, molded case circuit breaker, 3-pole, 800 A, ETU860 electronic trip unit, line protection, 187 kA at 240 V.","salesMarkdown":"The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V. Those numbers mean this breaker can clear a fault at full short-circuit capacity without upstream cascading — critical for high-fault panels fed by large transformers. It carries the ETU860 electronic trip unit, which gives you adjustable long-time pickup (Ir up to 800 A), long-time delay (tr from 0.5 s to 25 s), and short-time delay (tsd from 0.05 s to 0.5 s). That selectivity tuning is what lets you coordinate downstream feeders without nuisance trips. Communication function is onboard, so it can report status to a higher-level system. The 3VA2580-5KQ32-0HH0 measures 210 mm wide, 320 mm high, and 120 mm deep. Maximum power dissipation is 135 W at full rated current. For a main breaker that cycles infrequently (a few times a year for maintenance), that is effectively a lifetime rating. For a breaker used as a daily disconnect, it is still a solid figure.","metaTitle":"Siemens 3VA2580-5KQ32-0HH0 SENTRON MCCB, 800 A, 3-Pole, ETU8","metaDescription":"Siemens 3VA2580-5KQ32-0HH0 SENTRON molded case circuit breaker, 800 A rated continuous, 3-pole, ETU860 trip unit, 187 kA at 240 V. Current lifecycle, available to order. Request a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 690 V":"53 kA","at 40 °C":"800 A","at 45 °C":"800 A","at 50 °C":"800 A","at 55 °C":"800 A","at 60 °C":"800 A","at 65 °C":"767 A","at 70 °C":"703 A","Width [in]":"8.3 in","Height [in]":"12.6 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"10 000","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"135 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"800 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Summation current formation L-conductor","Design of the overcurrent release":"ETU860","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"Without","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"25","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Adjustable response value current / Ir max.":"800 A","Adjustable response value current / lg max.":"800 A","Adjustable response value current / lg min.":"160 A","Adjustable response value current / li max.":"8 000 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"320 A","Adjustable response value current / tg max.":"0.8 s","Adjustable response value current / tg min.":"0.05 s","Adjustable response value current / Isd max.":"8 000 A","Adjustable response value current / Isd min.":"480 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Protective function of the overcurrent release":"LSIG","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"1 000 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=646104&mlfb=3VA2580-5KQ32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2580-5KQ32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does this breaker use?","answer":"It uses the ETU860 electronic trip unit with adjustable long-time pickup (Ir up to 800 A), long-time delay (tr 0.5 s to 25 s), and short-time delay (tsd 0.05 s to 0.5 s)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2580-5KQ32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2580-5KQ32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}