{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2580-6JP32-0AL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2580-6JP32-0AL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2580-6JP32-0AL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2580-6JP32-0AL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 1000, breaking capacity class H, Icu=85kA @ 415V, 3-pole, line protection ETU550, LSI, In=800A, overload Ir=320A...800A.","salesMarkdown":"The Siemens 3VA2580-6JP32-0AL0 is a 3-pole IEC frame 1000 circuit breaker with breaking capacity class H, rated Icu=85kA at 415 V. It uses an ETU550 electronic trip unit configured for LSI protection — long-time (overload), short-time, and instantaneous — with a nominal current In=800 A and an adjustable overload protection range Ir=320 A…800 A. Short-circuit protection Isd is adjustable 0.6…10× In, and instantaneous pickup Ii ranges 1.5…12× In. The breaker also supports N-conductor protection via an external current transformer, up to 160% of In. ## Built-in auxiliaries and accessories That means the breaker arrives with its signaling and status feedback wired in — no separate ordering of aux blocks for basic panel indication.","metaTitle":"Siemens 3VA2580-6JP32-0AL0 Circuit Breaker, 85kA @ 415V, 800","metaDescription":"Siemens 3VA2580-6JP32-0AL0 IEC frame 1000 breaker, H class Icu=85kA @ 415V, 3-pole, ETU550 LSI, In=800A. Active lifecycle, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1544511&mlfb=3VA2580-6JP32-0AL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2580-6JP32-0AL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"It is rated Icu=85 kA at 415 V, which is breaking capacity class H on the IEC frame 1000 — suitable for high-fault-current installations like main switchboards or large distribution panels."},{"question":"What auxiliary contacts are included on this variant?","answer":"The breaker ships with 2 auxiliary switch changeover contacts (H), 1 trip alarm changeover contact, and 1 electrical alarm switch (HQ). No separate aux block purchase is needed for basic status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2580-6JP32-0AL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2580-6JP32-0AL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}