{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4110-5ED14-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4110-5ED14-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4110-5ED14-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4110-5ED14-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4110-5ED14-0AA0, 1-pole molded-case circuit breaker, 100 A at 40 °C, TM210 thermal-magnetic release, 85 kA at 120 V interrupting capacity, IP40 front protection.","salesMarkdown":"The Siemens 3VA4110-5ED14-0AA0 is a 1-pole SENTRON molded-case circuit breaker (MCCB) rated 100 A continuous at 40 °C ambient, with a TM210 thermal-magnetic release. The interrupting capacity is 85 kA at 120 V AC, 35 kA at 277 V, and 18 kA at 347 V; at 415 V operating voltage the breaker still clears high-fault scenarios common in industrial distribution. The single-pole footprint is 25.4 mm wide — one standard DIN module — so it slots into a panel without eating extra rail space. ## What it does not carry This is a straight system-protection MCCB — overload and short-circuit only. If the BOM calls for shunt trip or remote signaling, this is not that variant.","metaTitle":"Siemens 3VA4110-5ED14-0AA0 SENTRON MCCB, 1-pole, 100 A, 85 k","metaDescription":"Siemens 3VA4110-5ED14-0AA0 SENTRON molded-case circuit breaker, 1-pole, 100 A at 40 °C, TM210 release, 85 kA at 120 V interrupting capacity. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"25.4 mm","title":"3VA4110-5ED14-0AA0","Height":"129.4 mm","Maximum":"1 s","Minimum":"1 s","at 120 V":"85 kA","at 277 V":"35 kA","at 347 V":"18 kA","at 40 °C":"100 A","at 45 °C":"98 A","at 50 °C":"96 A","at 55 °C":"93 A","at 60 °C":"91 A","at 65 °C":"89 A","at 70 °C":"87 A","Depth [In]":"2.96 in","Width [In]":"1 in","Height [In]":"5.09 in","description":"circuit breaker 3VA4 UL frame 125 breaking capacity class M 35kA @ 277 V 1-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A fixed short-circuit protection Ii=10 x In clamp connection","Trip Indicator":"No","Number Of Poles":"1","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Design Of The Product":"System protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"MEAB","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","electrical endurance (operating cycles) / at 480 V":"8 000","electrical endurance (operating cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e3c5a0db84926dee35e456cc1567cb64.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058300&mlfb=3VA4110-5ED14-0AA0"},"ai":{"faq":[{"question":"What is 3VA4110-5ED14-0AA0's listed depth?","answer":"75.1 mm. That is the body depth from the DIN-rail mounting surface to the front of the breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4110-5ED14-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4110-5ED14-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}