{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4110-6ED24-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4110-6ED24-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4110-6ED24-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4110-6ED24-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4110-6ED24-1AA0, Molded-case circuit breaker, System protection, 2-pole, 100 A, 100 kA at 240 V, TM210 release.","salesMarkdown":"## Siemens 3VA4110-6ED24-1AA0 — SENTRON 2-Pole MCCB, 100 A Frame The Siemens 3VA4110-6ED24-1AA0 is a 2-pole SENTRON molded-case circuit breaker (MCCB) in the System Protection product version, rated for continuous current of 100 A at 40 °C and carrying a 100 kA interrupting capacity at 240 V. It uses the TM210 thermal-magnetic overcurrent release — a fixed thermal element with adjustable magnetic trip — so the long-time pickup is fixed at 100 A, while the instantaneous magnetic trip is adjustable between 1000 A and 1000 A (fixed at 10x In for this release variant). The interrupting rating steps down with system voltage: 65 kA at 480 V, and 25 kA at 600 Y/347 V, which covers most North American 480/277 V distribution panels and 600 V class industrial feeds. ## Thermal Derating and Ambient Performance The breaker holds its full 100 A rating through 50 °C ambient, then derates linearly: 98 A at 55 °C, 96 A at 60 °C, 93 A at 65 °C, and 91 A at 70 °C — useful when the MCCB is mounted in a crowded enclosure or near heat sources. Operating ambient range is -25 °C to +70 °C, with storage from -40 °C to +80 °C; the 15.2 W maximum power loss at rated load should be factored into the enclosure thermal budget. Dimensions are 129.4 mm high, 50.8 mm wide, and 75.1 mm deep — a 2-inch wide footprint that fits standard MCCB panel cutouts and leaves room for side-by-side mounting on a DIN rail or direct panel mount.","metaTitle":"Siemens 3VA4110-6ED24-1AA0 SENTRON MCCB, 100A, 2-Pole","metaDescription":"Siemens 3VA4110-6ED24-1AA0 SENTRON molded-case circuit breaker, 2-pole, 100A rated, 100kA at 240V. TM210 release. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"50.8 mm","Height":"129.4 mm","at 240 V":"100 kA","at 480 V":"65 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"93 A","at 70 °C":"91 A","Depth [In]":"3 in","Width [In]":"2 in","Height [In]":"5.1 in","at 480 Y/277 V":"65 kA","at 600 Y/347 V":"25 kA","Number Of Poles":"2","Product version":"System protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"15.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / lg min.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","marking / acc. to UL 489 / 100%-rated breaker":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","electrical endurance (switching cycles) / at 480 V":"8 000","electrical endurance (switching cycles) / at 600 V":"4 000","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Arrangement Of Electrical Connectors / For Main Current Circuit":"Load side: Circular conductor terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (8 AWG - 3/0)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e3c5a0db84926dee35e456cc1567cb64.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058310&mlfb=3VA4110-6ED24-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4110-6ED24-1AA0/alternatives.json"},"ai":{"faq":[{"question":"Will the 3VA4110-6ED24-1AA0 drop into a panel specified for a 3VA1110-5EF32-0LA0?","answer":"The 3VA4110-6ED24-1AA0 is a 2-pole 100 A frame with a TM210 release, while the 3VA1110-5EF32-0LA0 is a different frame size and pole configuration — physical fit and wiring differ. A direct drop-in without rewiring is not expected; verify the mounting footprint and bus bar spacing before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4110-6ED24-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4110-6ED24-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}