{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4111-6ED14-3AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4111-6ED14-3AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4111-6ED14-3AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4111-6ED14-3AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA4 UL Frame 125, circuit breaker, breaking capacity class H 65 kA @ 277 V, 1-pole, line protection TM210, FTFM, In=110 A, overload protection Ir=110 A permanently set, short-circuit protection Ii=10 x In.","salesMarkdown":"The Siemens 3VA4111-6ED14-3AA0 is a 1-pole circuit breaker from the 3VA4 series, built on a UL Frame 125 platform. The TM210 thermal-magnetic trip unit is fixed at 110 A overload (Ir=110 A permanently set) with a short-circuit pickup of 10× In (Ii=10 x In), so it's sized for a 110 A continuous load and will hold through motor inrush up to roughly 1100 A before instantaneous trip. ## Compliance & Regulatory RoHS compliant since 13-05-19. Export Control Regulations: AL N / ECCN EAR99 — no special licensing required for most destinations. ## Integration Note The 1-pole form factor fits a single module width in the 3VA4 family. For a 110 A feeder on a 277 V line, verify that the panel SCCR rating is at least 65 kA at that voltage — this breaker is the interrupting device, not the withstand rating of the bus. Terminal lug sizing for 110 A should match the wire gauge range in the installation instructions.","metaTitle":"Siemens 3VA4111-6ED14-3AA0 Circuit Breaker, 65 kA @ 277 V, 1","metaDescription":"Siemens 3VA4111-6ED14-3AA0 circuit breaker, 3VA4 UL Frame 125, 65 kA @ 277 V, 1-pole, TM210, In=110 A. Active production, RoHS compliant. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Group Code":"P360","Product Group":"5385","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Ordering Data Overview","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99","Packaging dimensions (L x W x H)":"472.00 x 396.00 x 213.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 13-05-19","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a94ec455330b880c206dcafa891b41ba.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/3VA4111-6ED14-3AA0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4111-6ED14-3AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA4111-6ED14-3AA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 3VA4111-6ED14-3AA0?","answer":"RoHS compliance is confirmed since 13-05-19. The part contains lead above 0.1% w/w, triggering REACH Article 33 notification. Export classification is AL N / ECCN EAR99."},{"question":"What is the group code and product group for this part?","answer":"The group code is P360 and the product group is 5385 on the Siemens catalog line."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4111-6ED14-3AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4111-6ED14-3AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}