{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4130-4ED34-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4130-4ED34-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4130-4ED34-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4130-4ED34-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4130-4ED34-0AA0, molded-case circuit breaker, 3-pole, 30 A at 40 °C, 65 kA at 240 V, 25 kA at 480 V, TM210 release, IP40 front.","salesMarkdown":"It is rated 30 A at 40 °C, with interrupting capacity of 65 kA at 240 V AC and 25 kA at 480 V AC — figures that govern its use as a main or feeder breaker in distribution panels where fault current levels are known. At 240 V the breaker clears 65 kA; at 480 V that drops to 25 kA, and at 600Y/347 V it is 14 kA. Current rating is temperature-dependent: 30 A at 40 °C, derating to 29 A at 45–50 °C, 28 A at 55 °C, 27 A at 60–65 °C, and 26 A at 70 °C. Dimensions are 76.2 mm wide, 129.4 mm high, and 75.1 mm deep — a standard 3-pole MCCB footprint that fits most Siemens SENTRON panelboards and distribution blocks. The breaker is rated for 690 V AC and carries UL file SEAB, confirming UL 489 listing for the US market.","metaTitle":"Siemens SENTRON 3VA4130-4ED34-0AA0 MCCB, 30 A, 65 kA at 240","metaDescription":"Siemens SENTRON 3VA4130-4ED34-0AA0 molded-case circuit breaker, 3-pole, 30 A at 40 °C, 65 kA at 240 V, 25 kA at 480 V. TM210 release. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"76.2 mm","Height":"129.4 mm","at 240 V":"65 kA","at 480 V":"25 kA","at 40 °C":"30 A","at 45 °C":"29 A","at 50 °C":"29 A","at 55 °C":"28 A","at 60 °C":"27 A","at 65 °C":"27 A","at 70 °C":"26 A","Depth [In]":"2.96 in","Width [In]":"3 in","Height [In]":"5.09 in","Trip Indicator":"No","at 480 Y/277 V":"25 kA","at 600 Y/347 V":"14 kA","Number Of Poles":"3","Product version":"System protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"SEAB","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","electrical endurance (switching cycles) / at 480 V":"8 000","electrical endurance (switching cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (14 AWG - 8 AWG)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f5f9416f23e44383b2107af7db46916.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058185&mlfb=3VA4130-4ED34-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4130-4ED34-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA4130-4ED34-0AA0 at 480 V?","answer":"25 kA at 480 V AC, and 25 kA at 480Y/277 V."},{"question":"Where can I buy 3VA4130-4ED34-0AA0?","answer":"This part is sourced to order through independent distribution channels. Submit an RFQ for current availability and pricing."},{"question":"What compliance documentation is available for this breaker?","answer":"The breaker carries UL file SEAB (UL 489 listing) and is rated for 690 V AC. RoHS and REACH compliance documentation is typically provided by the manufacturer for the SENTRON series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4130-4ED34-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4130-4ED34-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}