{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4130-6ED24-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4130-6ED24-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4130-6ED24-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4130-6ED24-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4130-6ED24-1AA0, 2-pole molded-case circuit breaker, 30 A, TM210 release, 100 kA at 240 V AC, 65 kA at 480 V AC, IP40 front, current production.","salesMarkdown":"It's rated 30 A continuous at 40 °C and holds that rating flat through 50 °C, then derates to 27 A at 70 °C — so in a warm panel you still get full ampacity up to 50 °C ambient. Interrupting capacity is 100 kA at 240 V AC and 65 kA at 480 V AC; that 100 kA figure at 240 V means it handles high-fault scenarios common in North American 120/240 V split-phase or 240 V delta services without needing a current-limiting upstream device. ## SCCR and selectivity For panel builders chasing a 65 kA SCCR at 480 V, this MCCB delivers it without series rating — the 65 kA at 480 V is its standalone interrupting rating. At 600Y/347 V it still manages 25 kA, which covers most 600 V class wye services. The TM210 release's magnetic pickup is fixed, so coordination with downstream branch breakers depends on the let-through energy at your available fault current; the 100 kA at 240 V makes it a strong main for 240 V distribution panels feeding multiple smaller breakers. Width is 50.8 mm (2 in), height 129.4 mm (5.09 in), depth 75.1 mm (2.96 in). Front protection is IP40. No trip indicator or undervoltage release. UL file HEAM is on record — that's the UL 489 listing for molded-case circuit breakers. The product designation per UL file confirms it carries the HEAM category, which covers MCCBs for branch circuit protection. Operating voltage is rated 415 V AC; the interrupting ratings at 240 V, 480 V, and 600Y/347 V cover the common North American and international voltage classes. RoHS and REACH compliance is standard for current-production SENTRON parts, though the specific declarations are issued per shipment lot.","metaTitle":"Siemens 3VA4130-6ED24-1AA0 SENTRON MCCB, 30 A, 100 kA at 240","metaDescription":"Siemens SENTRON 3VA4130-6ED24-1AA0 molded-case circuit breaker, 2-pole, 30 A, 100 kA at 240 V AC. TM210 release. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"50.8 mm","title":"3VA4130-6ED24-1AA0","Height":"129.4 mm","at 240 V":"100 kA","at 480 V":"65 kA","at 40 °C":"30 A","at 45 °C":"30 A","at 50 °C":"30 A","at 55 °C":"29 A","at 60 °C":"29 A","at 65 °C":"28 A","at 70 °C":"27 A","Depth [In]":"2.96 in","Width [In]":"2 in","Height [In]":"5.09 in","description":"circuit breaker 3VA4 UL frame 125 breaking capacity class H 65kA @ 480 V 2-pole, line protection TM210, FTFM, In=30A overload protection Ir=30A fixed short-circuit protection Ii=10 x In UL489 SB (naval), 50 deg. cel. clamp connection","Trip Indicator":"No","at 480 Y/277 V":"65 kA","at 600 Y/347 V":"25 kA","Number Of Poles":"2","Product version":"System protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"HEAM","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","electrical endurance (switching cycles) / at 480 V":"8 000","electrical endurance (switching cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (14 AWG - 8 AWG)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f5f9416f23e44383b2107af7db46916.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058198&mlfb=3VA4130-6ED24-1AA0"},"ai":{"faq":[{"question":"Does the 3VA4130-6ED24-1AA0 have an undervoltage release?","answer":"No, this variant does not include an undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4130-6ED24-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4130-6ED24-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}