{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4130-6ED34-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4130-6ED34-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4130-6ED34-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4130-6ED34-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4130-6ED34-0AA0, molded-case circuit breaker, 3-pole, TM210 overcurrent release, rated 30 A at 40 °C, interrupting capacity 100 kA at 240 V AC, 65 kA at 480 V AC.","salesMarkdown":"The Siemens SENTRON 3VA4130-6ED34-0AA0 is a 3-pole molded-case circuit breaker (MCCB) with a TM210 thermal-magnetic overcurrent release, designed for system protection in distribution panels and motor branch circuits. It carries a continuous current rating of 30 A at 40 °C, derating to 26 A at 70 °C — a curve worth checking if the panel runs hot. The interrupting capacity is 100 kA at 240 V AC and 65 kA at 480 V AC, which gives solid SCCR headroom for most industrial service-entrance and feeder applications. At 240 V AC this breaker clears 100 kA symmetrical — that's full-rated for a 100 kA SCCR panel. At 480 V AC it still handles 65 kA, which covers most 480 V distribution boards without an upstream current-limiting fuse. The 65 kA figure repeats at 480Y/277 V; at 600Y/347 V it drops to 25 kA, so check the available fault current if the system runs at 600 V class. At 45 °C it's 29 A, at 55 °C it's 28 A, at 70 °C it's 26 A. Operating range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Front IP40 means it's splash-resistant in the panel face but not washdown-rated.","metaTitle":"Siemens SENTRON 3VA4130-6ED34-0AA0 MCCB, 30A, 100kA at 240V","metaDescription":"Siemens SENTRON 3VA4130-6ED34-0AA0 molded-case circuit breaker, 3-pole, 30A rated at 40°C, 100kA at 240V AC, TM210 release. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"76.2 mm","title":"3VA4130-6ED34-0AA0","Height":"129.4 mm","Maximum":"1 s","Minimum":"1 s","at 240 V":"100 kA","at 480 V":"65 kA","at 40 °C":"30 A","at 45 °C":"29 A","at 50 °C":"29 A","at 55 °C":"28 A","at 60 °C":"27 A","at 65 °C":"27 A","at 70 °C":"26 A","Depth [In]":"2.96 in","Width [In]":"3 in","Height [In]":"5.09 in","description":"circuit breaker 3VA4 UL frame 125 breaking capacity class H 65kA @ 480 V 3-pole, line protection TM210, FTFM, In=30A overload protection Ir=30A fixed short-circuit protection Ii=10 x In clamp connection","Trip Indicator":"No","at 480 Y/277 V":"65 kA","at 600 Y/347 V":"25 kA","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Design Of The Product":"System protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"HEAB","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","electrical endurance (operating cycles) / at 480 V":"8 000","electrical endurance (operating cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$124.46","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f5f9416f23e44383b2107af7db46916.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058199&mlfb=3VA4130-6ED34-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA4130-6ED34-0AA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the interrupting capacity of this MCCB at 480 V?","answer":"At 480 V AC (and 480Y/277 V) the interrupting capacity is 65 kA symmetrical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4130-6ED34-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4130-6ED34-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}