{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4130-6ED34-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4130-6ED34-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4130-6ED34-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4130-6ED34-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4130-6ED34-1AA0, 3-pole molded-case circuit breaker, 30 A, 100 kA at 240 V, TM210 thermal-magnetic release, LI protection.","salesMarkdown":"The Siemens SENTRON 3VA4130-6ED34-1AA0 is a 3-pole molded-case circuit breaker rated 30 A continuous at 40 °C, with a TM210 thermal-magnetic release set for LI (long-time and instantaneous) protection. The instantaneous pickup is fixed at 300 A — no adjustment range, so it trips fast on a hard fault. At 65 kA at 480 V, this breaker can sit at the main lug of a panel fed from a 500 kVA transformer without worrying about cascading failure. The 100 kA at 240 V covers the worst-case bolted fault on a 208Y/120 V secondary — common in North American commercial and industrial switchboards. At 55 °C it derates to 29 A, at 65 °C to 28 A, and at 70 °C to 27 A. That flat curve means you can pack it into a warm enclosure — say a non-ventilated panel near a drive or transformer — and still count on nearly full rating. The 76.2 mm width (3 in) and 75.1 mm depth (3 in) fit standard MCCB mounting footprints; the 129.4 mm height (5.1 in) clears most distribution panel gutters.","metaTitle":"Siemens 3VA4130-6ED34-1AA0 SENTRON MCCB, 30 A, 100 kA at 240","metaDescription":"Siemens 3VA4130-6ED34-1AA0 SENTRON molded-case circuit breaker, 3-pole, 30 A, 100 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"76.2 mm","title":"3VA4130-6ED34-1AA0","Height":"129.4 mm","at 240 V":"100 kA","at 480 V":"65 kA","at 40 °C":"30 A","at 45 °C":"30 A","at 50 °C":"30 A","at 55 °C":"29 A","at 60 °C":"29 A","at 65 °C":"28 A","at 70 °C":"27 A","Depth [In]":"3 in","Width [In]":"3 in","Height [In]":"5.1 in","description":"circuit breaker 3VA4 UL frame 125 breaking capacity class H 65kA @ 480 V 3-pole, line protection TM210, FTFM, In=30A overload protection Ir=30A fixed short-circuit protection Ii=10 x In UL489 SB (naval), 50 deg. cel. clamp connection","at 480 Y/277 V":"65 kA","at 600 Y/347 V":"25 kA","Number Of Poles":"3","Product version":"System protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"30 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"300 A","Adjustable response value current / li min.":"300 A","marking / acc. to UL 489 / 100%-rated breaker":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"125 A","electrical endurance (switching cycles) / at 480 V":"8 000","electrical endurance (switching cycles) / at 600 V":"4 000","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Arrangement Of Electrical Connectors / For Main Current Circuit":"Load side: Circular conductor terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (14 AWG - 8 AWG)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f5f9416f23e44383b2107af7db46916.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058200&mlfb=3VA4130-6ED34-1AA0"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA4130-6ED34-1AA0 at 240 V and 480 V?","answer":"100 kA at 240 V and 65 kA at 480 V, making it suitable for high-fault-current panels."},{"question":"What is the continuous current rating of 3VA4130-6ED34-1AA0?","answer":"30 A at 40 °C, with minimal derating up to 70 °C ambient."},{"question":"Where can I buy 3VA4130-6ED34-1AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4130-6ED34-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4130-6ED34-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}