{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4140-6ED24-3AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4140-6ED24-3AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4140-6ED24-3AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4140-6ED24-3AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA4 UL Frame 125, 2-pole circuit breaker, breaking capacity class H 65 kA @ 480 V, line protection TM210, FTFM, In=40 A, overload protection Ir=40 A permanently set, short-circuit protection Ii=10 x In.","salesMarkdown":"The Siemens 3VA4140-6ED24-3AA0 is a 2-pole UL Frame 125 molded-case circuit breaker with a 65 kA interrupting capacity at 480 VAC — that is Class H breaking capacity, meaning it can safely clear a 65 kA fault without venting or cascading to upstream devices. The TM210 thermal-magnetic trip unit is set with a fixed Ir of 40 A (overload protection) and a fixed short-circuit pickup Ii of 10 x In, so it holds steady for motor inrush and trips fast on a bolted fault. This is a line-protection breaker, not a motor-circuit protector; the FTFM (fixed thermal, fixed magnetic) configuration means no field-adjustable dials — what you order is what you get.","metaTitle":"Siemens 3VA4140-6ED24-3AA0 Circuit Breaker, 65 kA @ 480 V, 4","metaDescription":"Siemens 3VA4140-6ED24-3AA0 circuit breaker, 2-pole, 65 kA @ 480 V, TM210 trip unit, Ir=40 A fixed. Active production. Sourced to order. RoHS compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Group Code":"P360","Product Group":"5385","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Ordering Data Overview","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99","Packaging dimensions (L x W x H)":"472.00 x 396.00 x 213.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 13-05-19","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/97bf270ad284f8c208f165c975f5f84a.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/3VA4140-6ED24-3AA0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4140-6ED24-3AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of this breaker?","answer":"It is rated 65 kA at 480 VAC, which is the Class H breaking capacity for the 3VA4 UL Frame 125."},{"question":"Where can I buy 3VA4140-6ED24-3AA0?","answer":"This part is sourced to order against an RFQ through our authorized distribution network. Submit a request for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4140-6ED24-3AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4140-6ED24-3AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}