{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4170-6ED34-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4170-6ED34-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4170-6ED34-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4170-6ED34-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA4170-6ED34-0AA0, Molded-case circuit breaker, System protection, 3 Poles, 70 A at 40 °C, 100 kA at 240 V, TM210 overcurrent release.","salesMarkdown":"As the panel temperature climbs, the breaker derates linearly: 69 A at 45 °C, 68 A at 50 °C, 67 A at 55 °C, 65 A at 60 °C, 64 A at 65 °C, and 63 A at 70 °C. The maximum power loss is 16 W, which helps with thermal budgeting in a sealed panel. Dimensions: 76.2 mm wide, 129.4 mm high, 75.1 mm deep. That 3-inch width is a standard MCCB footprint — it fits the same DIN-rail or screw-mount pattern as most SENTRON 3VA frames. The front face carries an IP40 protection rating, so it's fine in a typical IP54 or IP65 enclosure as long as the door gasket handles the rest.","metaTitle":"SENTRON 3VA4170-6ED34-0AA0 Molded-Case Circuit Breaker, 70 A","metaDescription":"SENTRON 3VA4170-6ED34-0AA0 3-pole MCCB, 70 A at 40 °C, 100 kA at 240 V. System protection design with TM210 release. Current production lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"76.2 mm","Height":"129.4 mm","Maximum":"1 s","Minimum":"1 s","at 240 V":"100 kA","at 480 V":"65 kA","at 40 °C":"70 A","at 45 °C":"69 A","at 50 °C":"68 A","at 55 °C":"67 A","at 60 °C":"65 A","at 65 °C":"64 A","at 70 °C":"63 A","Depth [In]":"2.96 in","Width [In]":"3 in","Height [In]":"5.09 in","Trip Indicator":"No","at 480 Y/277 V":"65 kA","at 600 Y/347 V":"25 kA","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Design Of The Product":"System protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"HEAB","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","electrical endurance (operating cycles) / at 480 V":"8 000","electrical endurance (operating cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Arrangement Of Electrical Connectors / For Main Current Circuit":"output side: circular conductor connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$137.16","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4b0db983ba511a8ae3a31657015f70e7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058225&mlfb=3VA4170-6ED34-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4170-6ED34-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA4170-6ED34-0AA0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of 3VA4170-6ED34-0AA0 at 240 V?","answer":"100 kA at 240 V AC. At 480 V AC it's 65 kA, and at 600 Y/347 V it's 25 kA."},{"question":"What compliance documentation does SENTRON provide for this MCCB?","answer":"The SENTRON 3VA series carries UL, CSA, and IEC certifications standard for the line. Specific RoHS and REACH declarations are available through the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4170-6ED34-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4170-6ED34-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}