{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4190-6ED14-3AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4190-6ED14-3AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4190-6ED14-3AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4190-6ED14-3AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA4 UL Frame 125, 1-pole circuit breaker, 90 A, 65 kA @ 277 V, TM210 trip unit, line protection.","salesMarkdown":"The Siemens 3VA4190-6ED14-3AA0 is a 1-pole circuit breaker from the 3VA4 UL Frame 125 series, rated 90 A continuous with a 65 kA interrupting capacity at 277 V. The TM210 thermal-magnetic trip unit provides fixed overload protection at Ir=90 A and fixed short-circuit protection at Ii=10 × In (900 A). This is a line-protection breaker — sized for feeder or branch circuits where the load is known and the trip curve is set at the factory. ## Compliance and regulatory RoHS compliant since 13 May 2019.","metaTitle":"Siemens 3VA4190-6ED14-3AA0 Circuit Breaker, 90 A, 65 kA @ 27","metaDescription":"Siemens 3VA4190-6ED14-3AA0 3VA4 UL Frame 125 circuit breaker, 1-pole, 90 A, 65 kA interrupting at 277 V. Active production. Sourced to order. RoHS compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Group Code":"P360","Product Group":"5385","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Ordering Data Overview","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99","Packaging dimensions (L x W x H)":"472.00 x 396.00 x 213.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 13-05-19","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b48639d71779639d8f1aa0307f4f86d7.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/3VA4190-6ED14-3AA0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4190-6ED14-3AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA4190-6ED14-3AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of the 3VA4190-6ED14-3AA0?","answer":"It is a 1-pole, 90 A continuous rated breaker with a 65 kA interrupting capacity at 277 V. The TM210 trip unit has fixed overload protection at Ir=90 A and fixed short-circuit protection at Ii=10 × In (900 A)."},{"question":"What compliance documentation is available for this part?","answer":"RoHS compliance is confirmed since 13 May 2019. REACH Article 33 disclosure indicates Lead content above 0.1% w/w. Export control is AL: N / ECCN: EAR99."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4190-6ED14-3AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4190-6ED14-3AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}