{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4190-6ED34-3AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4190-6ED34-3AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4190-6ED34-3AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4190-6ED34-3AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA4 UL Frame 125, circuit breaker, breaking capacity class H 65 kA @ 480 V, 3-pole, line protection TM210, FTFM, In=90 A, overload protection Ir=90 A permanently set, short-circuit protection Ii=10 x In.","salesMarkdown":"The Siemens 3VA4190-6ED34-3AA0 is a 3-pole molded case circuit breaker in the 3VA4 UL Frame 125 series, rated 90 A continuous (In) with a fixed overload setting (Ir=90 A) and a short-circuit trip set at 10 times In (Ii=10 x In). The TM210 thermal-magnetic trip unit gives you a fixed thermal curve for overloads and a magnetic instantaneous pickup for shorts; no field-adjustable dials on the Ir or Ii, so what's on the nameplate is what protects the circuit. This breaker is built to UL 489 standards for North American panelboards and switchboards. The UL Frame 125 designation means it fits standard 125 A frame accessories and bus connections — a direct swap into existing 3VA4 or comparable UL 489 panels without bus rework. ## Compliance and export notes RoHS compliant since 13-05-19. ## Panel integration and handling Packaged individually, shipping dimensions 472 x 396 x 213 mm. The 3VA4 frame mounts via the standard 3-pole MCCB footprint — bolt-on or plug-in depending on the panel's bus adapter. Verify the line/load lug kit is ordered separately if not included; the breaker ships as a bare unit.","metaTitle":"Siemens 3VA4190-6ED34-3AA0 Circuit Breaker, 65 kA @ 480 V, 9","metaDescription":"Siemens 3VA4190-6ED34-3AA0 circuit breaker, 3VA4 UL Frame 125, 65 kA @ 480 V, 3-pole, In=90 A, TM210. Active production. Sourced to order. RoHS compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Group Code":"P360","Product Group":"5385","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Ordering Data Overview","lifecycle_stage":"current","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99","Packaging dimensions (L x W x H)":"472.00 x 396.00 x 213.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 13-05-19","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6c3ea55ad1f8df8b0b5b4c2290649f1.pdf","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/3VA4190-6ED34-3AA0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4190-6ED34-3AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA4190-6ED34-3AA0 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Because it is a C-product (manufactured to order), availability and current pricing are confirmed at quote time — it is not a stocked shelf item."},{"question":"What is the group code and product group for this part?","answer":"The group code is P360 and the product group is 5385 as listed on the Siemens line."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4190-6ED34-3AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4190-6ED34-3AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}