{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4195-4ED54-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4195-4ED54-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4195-4ED54-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4195-4ED54-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4195-4ED54-0AA0, molded-case circuit breaker, 1-pole, 15 A (40 °C), TM210 release, 65 kA at 120 V AC, 75.1 mm depth.","salesMarkdown":"## System protection MCCB with TM210 release Its TM210 thermal-magnetic release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit interruption. Rated 15 A at 40 °C, it derates to 13 A at 70 °C, so the actual ampacity in a warm panel is lower than the nameplate suggests — plan your load at the expected ambient, not the 40 °C reference. Interrupting capacity is 65 kA at 120 V AC, dropping to 25 kA at 277 V and 14 kA at 347 V. On a 415 V AC rated system, the available fault current must be coordinated with these numbers — if your panel SCCR exceeds 14 kA at 347 V, this breaker may not clear a bolted fault upstream. The 1-pole format fits a single-phase branch or a DC string (per the 3VA DC manual), but verify polarity and arc extinction for DC use. Width is 50.8 mm (2 in) — a standard 2-module DIN-rail footprint that matches other SENTRON 3VA breakers. Depth of 75.1 mm means it clears most 100 mm-deep enclosures, but check gland-plate clearance if the breaker is mounted near the back wall. IP40 on the front face protects against tools and solid objects larger than 1 mm; the rear is open to the panel interior, so the enclosure IP rating governs overall ingress protection. The TM210 release has no trip indicator and no undervoltage release, so a downstream contactor or shunt trip must handle remote opening. No ground-fault monitoring version is fitted; add an external GFCI module if ground-fault protection is required.","metaTitle":"Siemens 3VA4195-4ED54-0AA0 SENTRON MCCB, 15A 1-Pole TM210, 6","metaDescription":"Siemens 3VA4195-4ED54-0AA0 SENTRON molded-case circuit breaker, 1-pole, 15A rated at 40°C, TM210 thermal-magnetic release, 65kA interrupting at 120V AC. Current lifecycle. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"50.8 mm","Height":"129.4 mm","Maximum":"1 s","Minimum":"1 s","at 120 V":"65 kA","at 277 V":"25 kA","at 347 V":"14 kA","at 40 °C":"15 A","at 45 °C":"15 A","at 50 °C":"14 A","at 55 °C":"14 A","at 60 °C":"14 A","at 65 °C":"13 A","at 70 °C":"13 A","Depth [In]":"2.96 in","Width [In]":"2 in","Height [In]":"5.09 in","Trip Indicator":"No","Number Of Poles":"1","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Undervoltage Release":"No","Design Of The Product":"System protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"3.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"SEAB","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","electrical endurance (operating cycles) / at 480 V":"8 000","electrical endurance (operating cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/64b8a3dd65d7e0d19359ee8da9307512.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058276&mlfb=3VA4195-4ED54-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4195-4ED54-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA4195-4ED54-0AA0's interrupting capacity at 120 V?","answer":"65 kA at 120 V AC. At 277 V it drops to 25 kA, and at 347 V to 14 kA. The 415 V AC rated operating voltage requires coordination with the available fault current at that level."},{"question":"What is the thermal derating for this 15 A MCCB?","answer":"Rated 15 A at 40 °C and 45 °C. Derates to 14 A at 50 °C, 55 °C, and 60 °C, and to 13 A at 65 °C and 70 °C. Size the load at the expected panel ambient temperature, not the 40 °C reference."},{"question":"What compliance documentation is available for 3VA4195-4ED54-0AA0?","answer":"As a Siemens SENTRON MCCB, it carries CE marking for the European market and is designed to IEC/EN 60947-2. UL/CSA listings are standard for the 3VA4 series; specific certification details should be confirmed from the manufacturer's declaration or the product certificate available via Siemens Industry Online Support."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4195-4ED54-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4195-4ED54-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}