{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA4195-5ED34-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA4195-5ED34-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA4195-5ED34-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA4195-5ED34-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA4195-5ED34-0AA0, Molded-case circuit breaker, 3-pole, 15 A (Iu), TM210 thermal-magnetic release, 85 kA at 240 V, 35 kA at 480 V.","salesMarkdown":"The Siemens 3VA4195-5ED34-0AA0 is a 3-pole SENTRON molded-case circuit breaker (MCCB) rated for 15 A continuous current (Iu) at 40 °C, with a TM210 thermal-magnetic overcurrent release that provides fixed LI protection — thermal for overload, magnetic for short-circuit. The magnetic trip is fixed at 300 A (li), so it clears hard faults fast without nuisance trips on motor inrush. Breaking capacity is the headline number here: 85 kA at 240 V and 35 kA at 480 V (also 35 kA at 480Y/277 V, 18 kA at 600Y/347 V). The thermal derating curve matters for panel fit: full 15 A up to 45 °C, then 14 A from 50 °C to 60 °C, and 13 A at 65 °C to 70 °C. If your enclosure runs hot, you're not getting the full 15 A — plan your load accordingly. ## Panel integration and physical fit Dimensions are 76.2 mm wide, 129.4 mm tall, 75.1 mm deep — standard 3-pole MCCB footprint for a 15 A frame. No communication function, no motor drive option, no ground-fault monitoring version on this variant — it's a straight thermal-magnetic MCCB for basic feeder and branch protection. The TM210 release is fixed, not adjustable on the thermal side, so what you see is what you get for overload pickup.","metaTitle":"Siemens 3VA4195-5ED34-0AA0 SENTRON MCCB, 15 A, 85 kA at 240","metaDescription":"Siemens SENTRON 3VA4195-5ED34-0AA0 molded-case circuit breaker, 3-pole, 15 A continuous, TM210 release, 85 kA at 240 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"75.1 mm","Width":"76.2 mm","Height":"129.4 mm","at 240 V":"85 kA","at 480 V":"35 kA","at 40 °C":"15 A","at 45 °C":"15 A","at 50 °C":"14 A","at 55 °C":"14 A","at 60 °C":"14 A","at 65 °C":"13 A","at 70 °C":"13 A","Depth [In]":"3 in","Width [In]":"3 in","Height [In]":"5.1 in","at 480 Y/277 V":"35 kA","at 600 Y/347 V":"18 kA","Number Of Poles":"3","Product version":"System protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded-case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"9.8 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"15 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","protection class IP / on the front":"IP40","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","product designation / according to UL file":"MEAB","Adjustable response value current / li max.":"300 A","Adjustable response value current / li min.":"300 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational current of the frame size":"125 A","electrical endurance (switching cycles) / at 480 V":"8 000","electrical endurance (switching cycles) / at 600 V":"4 000","marking / according to UL 489 / 100%-rated breaker":"No","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Infeed side: Low tab","Arrangement Of Electrical Connectors / For Main Current Circuit":"Load side: Circular conductor terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (14 AWG - 8 AWG)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/64b8a3dd65d7e0d19359ee8da9307512.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1058281&mlfb=3VA4195-5ED34-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA4195-5ED34-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA4195-5ED34-0AA0 replace 5SQ2370-2YA04 in an existing panel?","answer":"The 3VA4195 is a different generation and footprint than the 5SQ2370 series. Panel fit and bus connections differ; verify mounting dimensions and terminal spacing before assuming a drop-in swap. The 3VA4195 is a current-production part; the 5SQ2370 is an older design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA4195-5ED34-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA4195-5ED34-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}