{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA9114-0RL20","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA9114-0RL20","canonicalUrl":"https://aoctrl.com/siemens/3VA9114-0RL20","factsUrl":"https://aoctrl.com/api/mcp/products/3VA9114-0RL20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCD520 Basic residual current protection module Type A, 4-pole, rated 160 A, adjustable residual current 0.03–5 A, adjustable non-tripping time 0–3000 ms, load-side mounted accessory for 3VA1.","salesMarkdown":"The Siemens SENTRON 3VA9114-0RL20 is the RCD520 Basic residual current protection module Type A, designed as a load-side mounted accessory for the 3VA1 molded case circuit breaker family. It handles a rated operational current of 160 A at AC and accepts supply from either top or bottom infeed. ## What the adjustable settings mean on the line The residual current response value is selectable across seven steps from 0.03 A up to 5 A. That 0.03 A setting catches the 30 mA threshold required for personnel protection in most IEC 60364 installations, while the higher steps let you coordinate with downstream RCDs or tolerate leakage from VFD-fed motors without nuisance tripping. The non-tripping time is adjustable from 0 ms to 3000 ms in eight steps — use the delay settings for selective coordination (S-type behavior) so a fault on a branch clears before this main module trips. ## Where this module fits in the panel This is a Type A RCD, meaning it detects AC sinusoidal residual currents plus pulsating DC residual currents — the minimum for circuits with single-phase rectifiers, switching power supplies, or variable-speed drives. It mounts via screw fixing and connects to the main circuit through busbar connection, so it bolts directly to the 3VA1 breaker's load side without additional wiring. ## Field-note: sealable and pre-alarm The module is sealable — important for installations that require tamper-evidence after commissioning, common in utility or metering applications. It also provides a pre-alarm indication at 30% of the set residual current value, giving early warning before a trip event. That pre-alarm can feed into a monitoring system or just light a local indicator so maintenance catches a degrading insulation condition before it shuts the line. ## Physical fit check The 4-pole configuration covers three-phase-plus-neutral circuits.","metaTitle":"Siemens SENTRON 3VA9114-0RL20 RCD module, Type A, 160 A, 4-p","metaDescription":"Siemens SENTRON 3VA9114-0RL20 residual current protection module Type A, 160 A rated, 4-pole, adjustable 0.03–5 A. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"4","Width":"101.6 mm","Height":"100 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$407.67","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a1bf2fde7c861ba899a23d3d06f02c1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=194568&mlfb=3VA9114-0RL20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA9114-0RL20/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA9114-0RL20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA9114-0RL20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}