{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA9164-0JA12","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA9164-0JA12","canonicalUrl":"https://aoctrl.com/siemens/3VA9164-0JA12","factsUrl":"https://aoctrl.com/api/mcp/products/3VA9164-0JA12","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, box terminal TS1.2, 4 units, 6…120 mm², accessories for 3VA2 160, torque 6 Nm on solid 6–16 mm².","salesMarkdown":"The Siemens 3VA9164-0JA12 is a SENTRON box terminal designated TS1.2, sold as a set of four units for terminating copper cables from 6 mm² up to 120 mm². It is an accessory specifically for the 3VA2 160 molded-case circuit breaker family. ## Terminal capacity and wire range The TS1.2 accepts solid copper from a minimum of 10 AWG up to a maximum of 10 AWG, stranded from 10 AWG minimum to 3/0 AWG maximum, and finely stranded from 10 AWG minimum to 3/0 AWG maximum. The box terminal design accommodates the full range with the listed torque values. Maximum busbar dimensions accepted are 3 to 6 pieces of 20 mm x 1 mm; minimum busbar dimensions are 2 pieces of 6 x 13 mm x 0.5 mm.","metaTitle":"Siemens 3VA9164-0JA12 Box Terminal TS1.2, 6–120 mm², SENTRON","metaDescription":"Siemens SENTRON box terminal TS1.2 for 3VA2 160 breakers. Accepts 6–120 mm² copper, torque spec 6 Nm on solid. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Solid":"6 - 16 mm²: 6 Nm","Maximum":"3 - 6x 20 mm x 1 mm","Minimum":"2 6 x 13 mm x 0.5 mm","Stranded":"10 - 4 AWG: 105 lb-in 3 - 3/0 AWG: 140 lb-in","Accessories":"Box terminal","Finely Stranded":"10 - 4 AWG: 105 lb-in 3 - 3/0 AWG: 140 lb-in","Stripped Length":"0.75 in","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"accessories","Designation / Of The Terminal":"TS1.2","For Copper Cable / Solid / Maximum":"10 AWG","For Copper Cable / Solid / Minimum":"10 AWG","For Copper Cable / Stranded / Maximum":"3/0 AWG","For Copper Cable / Stranded / Minimum":"10 AWG","For Copper Cable / Finely Stranded / Maximum":"3/0 AWG","For Copper Cable / Finely Stranded / Minimum":"10 AWG"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7828f5767c5355511e9e5561324a1d5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=459879&mlfb=3VA9164-0JA12","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA9164-0JA12/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA9164-0JA12 fit 3RT1054-6QP35 contactors?","answer":"No. The TS1.2 box terminal is designed specifically for the 3VA2 160 molded-case circuit breaker family, not for SIRIUS contactors like the 3RT1054-6QP35 which use screw-type terminals for main and auxiliary circuits."},{"question":"What torque should I use for solid copper?","answer":"For solid copper conductors from 6 to 16 mm², torque to 6 Nm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA9164-0JA12","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA9164-0JA12 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}