{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1010-2ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1010-2ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1010-2ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1010-2ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1010-2ED32-0AA0, 3-pole molded case circuit breaker, 100 A (40 °C), TM210 thermal-magnetic release, line protection design, IP40 front.","salesMarkdown":"It carries a TM210 thermal-magnetic release, so the thermal element handles sustained overloads and the magnetic element clears high-fault events fast. Rated 100 A continuous at 40 °C, and it holds that same 100 A at 45 °C and 50 °C — no early derating. At 55 °C it steps down to 98 A, then 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. ## Interrupting capacity by system voltage Breaking capacity varies with the available fault current at the installation point: 53 kA at 240 V AC, 32 kA at 415 V AC, 14 kA at 440 V AC, and 8 kA at 500 V AC. The 1 000 A maximum rating is the frame's ultimate interrupt capacity under the standard, not the continuous load. Width 76.2 mm (3 in), depth 70 mm (2.76 in), height 130 mm (5.12 in). That 3-inch width is the standard MCCB footprint for a 3-pole frame in this class — it occupies three 1-inch module spaces on the DIN rail or panel-mount adapter.","metaTitle":"Siemens SENTRON 3VM1010-2ED32-0AA0 MCCB, 100 A, 3-Pole, TM21","metaDescription":"Siemens SENTRON 3VM1010-2ED32-0AA0 molded case circuit breaker, 100 A at 40 °C, 3-pole, TM210 release, 53 kA at 240 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1010-2ED32-0AA0","Height":"130 mm","Maximum":"1 000 A","Minimum":"1 s","at 240 V":"53 kA","at 415 V":"32 kA","at 440 V":"14 kA","at 500 V":"8 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 3-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A, not adjustable short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"39 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"12 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25581d9101f3aca0119ff846180f55d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575349&mlfb=3VM1010-2ED32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VM1010-2ED32-0AA0 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity at 240 V?","answer":"53 kA at 240 V AC. At 415 V it is 32 kA, at 440 V it is 14 kA, and at 500 V it is 8 kA."},{"question":"What compliance documentation is available for this MCCB?","answer":"The SENTRON 3VM series carries IEC 60947-2 certification. Specific documentation (CE, UKCA, RoHS, REACH) is provided with the product; request compliance declarations at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1010-2ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1010-2ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}