{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1010-3ED36-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1010-3ED36-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3VM1010-3ED36-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1010-3ED36-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1010-3ED36-0AA2, molded case circuit breaker, 3-pole, 100 A, 76 kA at 240 V, TM210 release, line protection.","salesMarkdown":"Its TM210 thermal-magnetic release (LI characteristic) provides fixed thermal pickup and magnetic trip for short-circuit protection, with no ground-fault monitoring or communication module onboard. This is a straight-ahead distribution breaker for a 3-phase panel, sized to protect a 100 A feeder. ## Breaking capacity — the real-world fault rating Breaking capacity drops sharply as line voltage rises: 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V. These values are the Icu (ultimate breaking capacity) per IEC 60947-2; no Ics (service breaking capacity) is listed, so assume the standard 50% Icu for Ics unless the manual specifies otherwise. ## Thermal derating — don't ignore the ambient curve Rated 100 A up to 50 °C; above that, derate linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. The TM210 release is fixed, so you cannot adjust the thermal pickup — the derating is the only way to stay within the trip curve. Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth (2.8 inches). No neutral conductor upgrade path, no motor drive accessory option. The 3-pole form factor fits standard MCCB mounting bases in distribution boards; verify the bus-bar pitch matches 76.2 mm center-to-center before committing the cutout.","metaTitle":"Siemens 3VM1010-3ED36-0AA2 MCCB, 100 A, 76 kA at 240 V","metaDescription":"Siemens SENTRON 3VM1010-3ED36-0AA2 molded case circuit breaker, 3-pole, 100 A rated, 76 kA breaking at 240 V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1010-3ED36-0AA2","Height":"130 mm","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.8 in","Width [In]":"3 in","Height [In]":"5.1 in","description":"circuit breaker 3VM1 IEC frame 100 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A, not adjustable short-circuit protection Ii=10 x In terminal connection","Number Of Poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"39 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"690 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"250 V","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25581d9101f3aca0119ff846180f55d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=682745&mlfb=3VM1010-3ED36-0AA2"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3VM1010-3ED36-0AA2?","answer":"The 3VA1010-2ED32-0JA0 is a sibling in the same SENTRON family but carries a different release and accessory set. The 3VM1010-3ED36-0AA2 uses the TM210 thermal-magnetic release with LI protection; the 3VA variant may differ in trip curve options and auxiliary contact availability. Verify the specific release and pole configuration before substituting — the 3VM is the current line-protection build."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1010-3ED36-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1010-3ED36-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}