{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1010-3ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1010-3ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1010-3ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1010-3ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1010-3ED42-0AA0, 4-pole molded case circuit breaker, line protection, 1000 A, 76 kA at 240 V, TM210 release, IP40 front.","salesMarkdown":"Its interrupting capacity reaches 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 8 kA at 500 V — figures that define its fault-clearing capability across common distribution voltages. Continuous current capacity holds at 100 A from 40 °C through 50 °C, then steps down to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power dissipation is 39 W. For a 4-pole breaker at this frame size, the thermal curve is the binding constraint in a sealed or high-ambient enclosure — plan the panel's internal temperature rise against the 50 °C threshold before derating begins. ## Physical footprint and mounting The 4-pole width of roughly 4 inches is standard for this class of MCCB, so it fits existing SENTRON panel cutouts and bus-bar centers without re-drilling. No communication function, trip indicator, or voltage trigger is built in — this is a straight thermal-magnetic protector with no auxiliary electronics.","metaTitle":"Siemens SENTRON 3VM1010-3ED42-0AA0 4-Pole MCCB, 1000 A, 76 k","metaDescription":"Siemens SENTRON 3VM1010-3ED42-0AA0 4-pole molded case circuit breaker, 1000 A max, 76 kA breaking at 240 V. TM210 release, IP40 front. Current lifecycle. Quoted to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","title":"3VM1010-3ED42-0AA0","Height":"130 mm","Maximum":"1 000 A","Minimum":"1 s","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"8 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 100 breaking capacity class N Icu=25kA @ 415V 4-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A, not adjustable short-circuit protection Ii=10 x In N conductor unprotected nut keeper kit","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"39 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"12 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25581d9101f3aca0119ff846180f55d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575352&mlfb=3VM1010-3ED42-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VM1010-3ED42-0AA0 and how is it quoted?","answer":"The 3VM1010-3ED42-0AA0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial proposal."},{"question":"What is the breaking capacity of 3VM1010-3ED42-0AA0 at different voltages?","answer":"The interrupting capacity is 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 8 kA at 500 V — these values govern its fault-clearing capability at each distribution voltage level."},{"question":"What compliance documentation does this MCCB carry?","answer":"The SENTRON series carries UL, IEC, RoHS, and REACH declarations. Request the specific certificate bundle for 3VM1010-3ED42-0AA0 with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1010-3ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1010-3ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}