{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1010-4ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1010-4ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1010-4ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1010-4ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1010-4ED32-0AA0, molded case circuit breaker, 3-pole, 100 A rated, 121 kA at 240 VAC, line protection, current lifecycle.","salesMarkdown":"It carries a continuous current of 100 A up to 50 °C ambient, then derates to 91 A at 70 °C — so for a 100 A feeder in a warm panel, you need to account for the thermal curve above 55 °C where it drops to 98 A. The interrupting ratings are substantial: 121 kA at 240 VAC, 76 kA at 415 VAC, 40 kA at 440 VAC, and 12 kA at 500 VAC. ## Thermal-magnetic release and selectivity The overcurrent release is a TM210 — a thermal-magnetic type with a fixed time-delay short-circuit pickup. Minimum trip time is 1 s, so it coordinates with downstream breakers that clear faster. No ground-fault monitoring, no undervoltage release, no communication function — this is a straight line-protection MCCB, not a smart breaker. ## Mounting and environment Front protection is IP40 — suitable for a clean, dry panel interior but not washdown. No trip indicator, no voltage trigger.","metaTitle":"Siemens SENTRON 3VM1010-4ED32-0AA0 MCCB, 100 A, 3-Pole, 121","metaDescription":"Siemens SENTRON 3VM1010-4ED32-0AA0 molded case circuit breaker, 100 A rated, 3-pole, 121 kA at 240 VAC. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1010-4ED32-0AA0","Height":"130 mm","Maximum":"1 000 A","Minimum":"1 s","at 240 V":"121 kA","at 415 V":"76 kA","at 440 V":"40 kA","at 500 V":"12 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 100 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A, not adjustable short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"39 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"12 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25581d9101f3aca0119ff846180f55d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575006&mlfb=3VM1010-4ED32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VM1010-4ED32-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What are the key ratings for 3VM1010-4ED32-0AA0?","answer":"Rated 100 A continuous (derated above 50 °C), 3-pole, interrupting capacity 121 kA at 240 VAC, 76 kA at 415 VAC, 40 kA at 440 VAC, 12 kA at 500 VAC. Insulation voltage 800 V. Overcurrent release TM210 with minimum trip time 1 s."},{"question":"What is the depth of 3VM1010-4ED32-0AA0?","answer":"Depth is 70 mm."},{"question":"What is the width of 3VM1010-4ED32-0AA0?","answer":"Width is 76.2 mm."},{"question":"Will 3VM1010-4ED32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?","answer":"The 3VM1010-4ED32-0AA0 is a 3-pole 100 A MCCB with a TM210 release; the 3VA1110-5ED32-0AA0 is a different series with potentially different dimensions, accessory fit, and interrupting ratings. Panel compatibility requires checking the mounting footprint and busbar arrangement — not a guaranteed drop-in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1010-4ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1010-4ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}