{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1025-2ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1025-2ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1025-2ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1025-2ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VM1025-2ED42-0AA0, 4-pole molded case circuit breaker, TM210 release, 25 A at 40 °C, 53 kA at 240 V, 70 mm depth.","salesMarkdown":"Its headline interrupting capacity — 53 kA at 240 V AC — drops to 32 kA at 415 V and 14 kA at 440 V, so the voltage at the fault point governs whether this breaker clears a high-fault event without upstream coordination issues. At 500 V the rating is 8 kA, which still covers most industrial motor branch circuits. The TM210 thermal-magnetic release is fixed at 25 A continuous up to 50 °C ambient; above that it derates to 24 A at 55–60 °C and 23 A at 65–70 °C, so a panel sitting near a hot transformer or in a non-conditioned enclosure needs that headroom factored in. The breaker measures 70 mm deep, 101.6 mm wide, and 130 mm high — a 4-pole MCCB that fits standard DIN-rail or panel-mount enclosures. The 101.6 mm width (4 inches) matches the common 4-pole MCCB footprint, so it drops into existing cutouts without rework. No motor drive or communication function is fitted; it is a straight thermal-magnetic device with no add-on options for remote trip or ground-fault monitoring.","metaTitle":"SENTRON 3VM1025-2ED42-0AA0 4-Pole MCCB, 25 A, 53 kA at 240 V","metaDescription":"SENTRON 3VM1025-2ED42-0AA0 molded case circuit breaker, 4-pole, 25 A, 53 kA at 240 V. TM210 release. Current lifecycle. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","title":"3VM1025-2ED42-0AA0","Height":"130 mm","at 240 V":"53 kA","at 415 V":"32 kA","at 440 V":"14 kA","at 500 V":"8 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"24 A","at 65 °C":"23 A","at 70 °C":"23 A","Depth [In]":"2.8 in","Width [In]":"4 in","Height [In]":"5.1 in","description":"circuit breaker 3VM1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 4-pole, line protection TM210, FTFM, In=25A overload protection Ir=25A, not adjustable short-circuit protection Ii=12.8 x In N conductor unprotected nut keeper kit","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"9 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"690 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"12 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a01c343e64219cb56d770b674b9211ef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575358&mlfb=3VM1025-2ED42-0AA0"},"ai":{"faq":[{"question":"What is the depth of 3VM1025-2ED42-0AA0?","answer":"The depth is 70 mm (2.8 inches)."},{"question":"What is the width of 3VM1025-2ED42-0AA0?","answer":"The width is 101.6 mm (4 inches)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1025-2ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1025-2ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}