{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1063-2ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1063-2ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1063-2ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1063-2ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VM1063-2ED42-0AA0, molded case circuit breaker, 4-pole, 63 A at 40 °C, interrupting 53 kA at 240 V, TM210 release, IP40 front.","salesMarkdown":"The 3VM1063-2ED42-0AA0: The overcurrent release is a TM210 — thermal-magnetic, fixed at 63 A continuous, with an adjustable magnetic trip (li) up to 630 A. That li range covers motor inrush and transformer magnetizing peaks without nuisance tripping, but it's not a full electronic trip unit; you get thermal protection for overloads and magnetic for short-circuits, no ground-fault monitoring or communication function on this variant. Panel integration is straightforward: the breaker measures 101.6 mm wide by 130 mm tall by 70 mm deep — a 4-pole MCCB that fits standard distribution board cutouts. ## What the 3VA1010-2ED32-0JA0 comparison tells you The 3VA1010-2ED32-0JA0 is the closest functional peer in the SENTRON family — same 4-pole footprint, same TM release architecture, but a lower continuous rating (100 A frame vs 63 A frame on this 3VM). The 3VM1063 is the 63 A frame; the 3VA1010 is the 100 A frame. If your panel was specced around the 3VA1010, the 3VM1063 won't drop in without checking the bus bar ampacity and the load calcs — the 3VM is a smaller frame, physically narrower, so it may fit the same cutout but the lugs and bus spacing differ. Rewiring isn't guaranteed; compare the terminal centers and the mounting hole pattern before committing.","metaTitle":"SENTRON 3VM1063-2ED42-0AA0 MCCB, 63 A, 53 kA at 240 V","metaDescription":"SENTRON 3VM1063-2ED42-0AA0 molded case circuit breaker, 4-pole, 63 A continuous at 40 °C, interrupting 53 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"53 kA","at 415 V":"32 kA","at 440 V":"14 kA","at 500 V":"8 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.8 in","Width [In]":"4 in","Height [In]":"5.1 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"22 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"690 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"630 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"12 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8639f3adb4318cd5c0a3c2fbb67e9acd.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575374&mlfb=3VM1063-2ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1063-2ED42-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1063-2ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1063-2ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}