{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1110-3ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1110-3ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1110-3ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1110-3ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1110-3ED42-0AA0, Molded case circuit breaker, 4-pole, 100 A, TM210 thermal-magnetic release, breaking capacity 76 kA at 240 V AC, IP40 front.","salesMarkdown":"The Siemens 3VM1110-3ED42-0AA0 is a SENTRON molded case circuit breaker rated for 100 A continuous current at 40 °C, holding that rating flat through 50 °C before a gentle derating curve begins — 98 A at 55 °C, 96 A at 60 °C, down to 91 A at 70 °C. Four poles, TM210 thermal-magnetic trip unit, no ground-fault monitoring, no motor drive option — this is a straight line-protection MCCB for distribution panels where you need a clean 100 A feed with adjustable instantaneous pickup up to 1000 A. ## Breaking capacity by system voltage — the real SCCR story Interrupting capacity varies sharply with system voltage: 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V. On a 480 V panel you're between the 440 V and 500 V figures — plan conservatively. Dimensions are 101.6 mm wide by 130 mm tall by 70 mm deep — a standard 4-pole MCCB footprint that drops into SENTRON distribution blocks and panelboards without adapters. Front face carries IP40 protection; the rest of the enclosure is open to the panel interior, so mount where cabinet IP rating handles the environment.","metaTitle":"Siemens 3VM1110-3ED42-0AA0 SENTRON MCCB, 100A, 4-Pole, 76kA","metaDescription":"Siemens 3VM1110-3ED42-0AA0 SENTRON molded case circuit breaker, 100A continuous, 4-pole, TM210 release. Breaking capacity 76kA at 240V AC. Active production, sourced to order. Requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"12 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.8 in","Width [In]":"4 in","Height [In]":"5.1 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"690 V","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f0ee706be5ade96bbda51580efca6e9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575386&mlfb=3VM1110-3ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1110-3ED42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VM1110-3ED42-0AA0?","answer":"Continuous current 100 A at 40 °C, 4-pole, TM210 thermal-magnetic release, breaking capacity 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, 12 kA at 500 V. Rated insulation voltage 690 V."},{"question":"Where can I buy 3VM1110-3ED42-0AA0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VM1110-3ED42-0AA0 drop into a panel specified for 3VA1010-2ED32-0JA0?","answer":"Both are SENTRON 4-pole MCCBs in the same physical class, but the 3VA series uses a different trip-unit generation and optional accessories. Mechanical footprint is similar; verify busbar and lug positions against your panel layout before swapping."},{"question":"What compliance documentation does Siemens provide for 3VM1110-3ED42-0AA0?","answer":"As a SENTRON MCCB, it carries IEC 60947-2 certification. Standard Siemens documentation includes CE declaration, RoHS and REACH compliance statements, and the 3VM manual with coordination curves. Specific UL listing status should be confirmed against the nameplate marking."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1110-3ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1110-3ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}