{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1110-3EE36-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1110-3EE36-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3VM1110-3EE36-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1110-3EE36-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VM1 series molded case circuit breaker, 3-pole, 100 A continuous, class N breaking capacity 76 kA at 240 V AC, line protection TM220 release, front box terminals.","salesMarkdown":"The SENTRON 3VM1110-3EE36-0AA2 is a 3-pole molded case circuit breaker (MCCB) from the 3VM1 frame, rated for 100 A continuous current at 40 °C and carrying a class N breaking capacity of 76 kA at 240 V AC. It's a line-protection device with a TM220 thermal-magnetic release — the thermal element adjustable from 70 A to 100 A, the magnetic fixed at 10× In. That means for a 100 A feeder, the instantaneous trip sits at 1000 A, which keeps it selective downstream of most 160 A–250 A upstream breakers in a typical 480 V distribution panel. This MCCB's interrupting rating drops as voltage rises: 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V. If your SCCR study shows fault current above 53 kA at 415 V, you need the class S or H version. Above that, it steps down: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. ## What's in the box — connections and accessories The main circuit connects via box terminals on the front — standard for panel wiring with ring lugs or fork terminals. No auxiliary contacts come built in (0 CO contacts), and there's no provision for a motor drive or neutral conductor upgrade. Communication function is absent, so no Modbus or PROFIBUS integration here — it's a straight electromechanical breaker.","metaTitle":"SENTRON 3VM1110-3EE36-0AA2 MCCB, 100 A, 76 kA at 240 V","metaDescription":"SENTRON 3VM1110-3EE36-0AA2 molded case circuit breaker, 3-pole, 100 A, breaking capacity 76 kA at 240 V AC. Line protection TM220 release. Quoted to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"title":"3VM1110-3EE36-0AA2","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM220, ATFM, In=100A overload protection Ir=70A...100A short-circuit protection Ii=10 x In terminal connection","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"690 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM220","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product extension / optional / motor drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f0ee706be5ade96bbda51580efca6e9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=682765&mlfb=3VM1110-3EE36-0AA2"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VM1110-3EE36-0AA2 at 240 V?","answer":"At 240 V AC, the breaking capacity is 76 kA. At 415 V it drops to 53 kA, at 440 V to 32 kA, and at 500 V to 11.9 kA."},{"question":"Where can I buy 3VM1110-3EE36-0AA2?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the continuous current rating of 3VM1110-3EE36-0AA2?","answer":"The rated continuous current Iu is 100 A. It holds full 100 A from 40 °C to 50 °C, then derates to 91 A at 70 °C."},{"question":"Does 3VM1110-3EE36-0AA2 have auxiliary contacts or communication?","answer":"No. It comes with zero auxiliary contacts, no communication function, and no motor drive option. It is a standalone electromechanical breaker."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1110-3EE36-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1110-3EE36-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}