{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1110-4ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1110-4ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1110-4ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1110-4ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1110-4ED32-0AA0, 3-pole molded case circuit breaker, TM210 thermal-magnetic release, 100 A at 40 °C, 1 000 A frame, 121 kA at 240 V, line protection.","salesMarkdown":"It carries a 1 000 A frame with a TM210 thermal-magnetic release — meaning the trip curve is fixed, no interchangeable trip units. At 40 °C it's rated 100 A continuous, and it holds that rating through 50 °C before starting to derate: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. For a panel that runs warm, that derating curve tells you exactly where you lose headroom. ## Breaking capacity — what it means for fault duty Breaking capacity is voltage-dependent: 121 kA at 240 V, 76 kA at 415 V, 53 kA at 440 V, 12 kA at 500 V. At 415 V that 76 kA covers most industrial distribution transformer secondary faults without cascading upstream. At 500 V the 12 kA figure drops sharply — verify the available fault current if your system runs 480/500 V. The 3-pole width is standard for a 100 A frame MCCB — it fits a typical 3 x 25 mm DIN cutout or bolted panel mount.","metaTitle":"Siemens SENTRON 3VM1110-4ED32-0AA0 MCCB, 100 A, 1 000 A max","metaDescription":"Siemens SENTRON 3VM1110-4ED32-0AA0 molded case circuit breaker, 3-pole, TM210 release, 100 A at 40 °C, 121 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1110-4ED32-0AA0","Height":"130 mm","Maximum":"1 000 A","Minimum":"1 s","at 240 V":"121 kA","at 415 V":"76 kA","at 440 V":"53 kA","at 500 V":"12 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A, not adjustable short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f0ee706be5ade96bbda51580efca6e9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575391&mlfb=3VM1110-4ED32-0AA0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1110-4ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1110-4ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}