{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1110-5EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1110-5EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1110-5EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1110-5EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1110-5EE32-0AA0, molded case circuit breaker, 3-pole, 100 A rated, line protection, TM220 release, interrupting 187 kA at 240 V AC.","salesMarkdown":"Its TM220 thermal-magnetic overcurrent release handles both overload and short-circuit conditions without undervoltage or ground-fault monitoring. The interrupting capacity is 187 kA at 240 V AC, 121 kA at 415 V, 76 kA at 440 V, and 17 kA at 500 V — so it clears high-fault currents on the secondary side of a transformer or near a large service entrance. The breaker holds 100 A up to 50 °C ambient, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That means a panel running at 55 °C loses 2 A of headroom; at 70 °C you lose 9 A. Body dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or backplate layouts. Maximum power loss is 25 W, so factor that into enclosure ventilation.","metaTitle":"Siemens SENTRON 3VM1110-5EE32-0AA0 MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VM1110-5EE32-0AA0 molded case circuit breaker, 100 A rated, 3-pole, interrupting up to 187 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"1 000 A","Minimum":"1 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"76 kA","at 500 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f0ee706be5ade96bbda51580efca6e9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575399&mlfb=3VM1110-5EE32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1110-5EE32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VM1110-5EE32-0AA0 at 240 V?","answer":"187 kA at 240 V AC, with 121 kA at 415 V, 76 kA at 440 V, and 17 kA at 500 V."},{"question":"Where can I buy 3VM1110-5EE32-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1110-5EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1110-5EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}