{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1116-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1116-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1116-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1116-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1116-3ED22-0AA0, molded case circuit breaker, 2-pole, 160 A at 40 °C, 76 kA at 240 V, line protection.","salesMarkdown":"The Siemens SENTRON 3VM1116-3ED22-0AA0 is a 2-pole molded case circuit breaker (MCCB) rated 160 A at 40 °C, with a TM210 overcurrent release set for line protection (LI characteristic). It carries 76 kA breaking capacity at 240 V AC and 53 kA at 415 V AC — enough to clear high-fault conditions in distribution panels without cascading upstream. Rated insulation voltage is 500 V, maximum operating voltage 415 V AC, and DC operation up to 250 V is supported. The 160 A rating holds flat from 40 °C through 50 °C. Above that, it derates gradually: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. Operating ambient range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The breaker measures 130 mm high, 50.8 mm wide, and 70 mm deep. The 50.8 mm width is a standard 2-inch footprint for a 2-pole MCCB — it will drop into a panel cutout or DIN-rail adapter designed for that pitch without rework.","metaTitle":"Siemens 3VM1116-3ED22-0AA0 SENTRON MCCB, 160 A, 2-Pole, 76 k","metaDescription":"Siemens SENTRON 3VM1116-3ED22-0AA0 molded case circuit breaker, 160 A at 40 °C, 2-pole, 76 kA at 240 V. Active production. Available to order — RFQ for current pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","title":"3VM1116-3ED22-0AA0","Height":"130 mm","at 240 V":"76 kA","at 415 V":"53 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 2-pole, line protection TM210, FTFM, In=160A overload protection Ir=160A, not adjustable short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"2","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Max. rated operational voltage Ue with DC":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3f0ee706be5ade96bbda51580efca6e9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575037&mlfb=3VM1116-3ED22-0AA0"},"ai":{"faq":[{"question":"What are the key ratings for 3VM1116-3ED22-0AA0?","answer":"It is a 2-pole MCCB rated 160 A at 40 °C, with a breaking capacity of 76 kA at 240 V AC and 53 kA at 415 V AC. The overcurrent release is a TM210 with LI protection characteristic."},{"question":"What is the depth of 3VM1116-3ED22-0AA0?","answer":"The depth is 70 mm (2.76 inches)."},{"question":"What is the width of 3VM1116-3ED22-0AA0?","answer":"The width is 50.8 mm (2 inches)."},{"question":"Where can I buy 3VM1116-3ED22-0AA0 and get current pricing?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — the quote will confirm real-time supply and price."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1116-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1116-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}