{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1132-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1132-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1132-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1132-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1132-3ED22-0AA0, molded case circuit breaker, 2-pole, 32 A rated current, TM210 thermal-magnetic release, 76 kA at 240 V AC, IP40 front protection.","salesMarkdown":"## SENTRON 3VM1132-3ED22-0AA0 — 2-Pole MCCB, 32 A, TM210 Release It carries a 32 A rated current at 40 °C ambient, with thermal derating to 30 A at 70 °C — the full curve is 32 A from 40 °C through 50 °C, 31 A at 55 °C and 60 °C, then 30 A at 65 °C and 70 °C. That means the breaker holds its full rating across typical panel ambient conditions, only stepping down when the enclosure runs hot. Front protection is IP40; the rest of the enclosure is unrated, so it belongs inside a panel, not exposed to washdown. Dimensions are 70 mm deep, 50.8 mm wide, 130 mm high — a compact 2-pole footprint that fits standard Siemens SENTRON panel mounting. Maximum power loss is 7 W. Insulation voltage rated at 500 V. ## Integration — Panel Fit and Coordination This MCCB mounts in a standard SENTRON panel or distribution board. The 50.8 mm width (2 inches) matches the 2-pole module footprint; depth of 70 mm and height of 130 mm fit within typical enclosure clearances. The TM210 release is fixed-trip, so selectivity coordination with downstream breakers depends on the time-current curve of the thermal-magnetic element; consult the 3VM characteristic curves for your specific coordination study.","metaTitle":"Siemens 3VM1132-3ED22-0AA0 SENTRON MCCB, 2-Pole, 32A, 76kA a","metaDescription":"Siemens SENTRON 3VM1132-3ED22-0AA0 molded case circuit breaker, 2-pole, 32A rated at 40°C, 76kA breaking at 240V AC. TM210 release, IP40 front. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"320 A","Minimum":"1 s","at 240 V":"76 kA","at 415 V":"53 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c44489171b065db9ac94407a2317a7df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575048&mlfb=3VM1132-3ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1132-3ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the 3VM1132-3ED22-0AA0?","answer":"76 kA at 240 V AC and 53 kA at 415 V AC, per the listed ratings."},{"question":"Where can I buy the 3VM1132-3ED22-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does the 3VM1132-3ED22-0AA0 have a ground-fault monitoring function?","answer":"No, this variant is without ground-fault monitoring and without an undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1132-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1132-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}