{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1132-3ED26-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1132-3ED26-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3VM1132-3ED26-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1132-3ED26-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VM1 IEC frame 160, 2-pole circuit breaker, breaking capacity class N, Icu=25kA @ 415V, line protection TM210, FTFM, In=32A, Ir=32A, Ii=10 x In, terminal connection.","salesMarkdown":"The Siemens 3VM1132-3ED26-0AA2 is a 2-pole IEC molded-case circuit breaker in the 3VM1 series, built on a 160 A frame but fitted with a 32 A thermal-magnetic trip unit (TM210). It is rated for line protection where load current is fixed at 32 A and short-circuit protection is set at 10× In, non-adjustable. ## Integration notes Terminal connection type means it accepts standard lug or busbar connections; the 160 A frame gives mechanical headroom for higher-rated versions in the same panel layout. The fixed thermal setting (Ir = 32 A) and fixed magnetic pickup (Ii = 10 × In) simplify coordination — no dials to mis-set, but also no field adjustment if the load changes.","metaTitle":"Siemens 3VM1132-3ED26-0AA2 Circuit Breaker, 32A, 25kA @ 415V","metaDescription":"Siemens 3VM1132-3ED26-0AA2 circuit breaker, IEC frame 160, 2-pole, 32A, 25kA breaking capacity at 415V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c44489171b065db9ac94407a2317a7df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=682808&mlfb=3VM1132-3ED26-0AA2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1132-3ED26-0AA2/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VM1132-3ED26-0AA2?","answer":"The breaking capacity is 25 kA at 415 V AC (class N), suitable for industrial mains with high fault current potential."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1132-3ED26-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1132-3ED26-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}