{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1132-5EE36-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1132-5EE36-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3VM1132-5EE36-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1132-5EE36-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VM1 IEC frame 160, breaking capacity class M, 3-pole MCCB, 55kA @ 415V, In=32A, adjustable thermal overload Ir=22A-32A, fixed magnetic Ii=10xIn, line protection TM220, ATFM, terminal connection.","salesMarkdown":"The 3VM1132-5EE36-0AA2 is a Siemens 3VM1 IEC frame 160 molded case circuit breaker, 3-pole, with a 55 kA breaking capacity at 415 V (class M). The thermal-magnetic trip unit (TM220, ATFM) gives adjustable overload protection from 22 A to 32 A, so you set the Ir dial to match your load's full-load amps, and a fixed magnetic short-circuit pickup at 10 x In (320 A) for instantaneous clearing on hard faults. ## Deployment context The terminal connection style accepts standard lug or busbar, common in distribution boards and motor control centers where you need coordinated short-circuit protection downstream of a main breaker.","metaTitle":"Siemens 3VM1132-5EE36-0AA2 Circuit Breaker, 55kA @ 415V, 32A","metaDescription":"Siemens 3VM1132-5EE36-0AA2 IEC 3-pole molded case circuit breaker, 55kA breaking capacity at 415V, 32A adjustable thermal-magnetic protection. Current production. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c44489171b065db9ac94407a2317a7df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=682813&mlfb=3VM1132-5EE36-0AA2","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1132-5EE36-0AA2/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VM1132-5EE36-0AA2?","answer":"The breaking capacity is 55 kA at 415 V, class M per IEC. That is the maximum fault current the breaker can safely interrupt at that voltage."},{"question":"What are the adjustable trip settings?","answer":"Overload protection (Ir) is adjustable from 22 A to 32 A via the thermal dial. Short-circuit protection (Ii) is fixed at 10 x In, or 320 A."},{"question":"Where can I buy 3VM1132-5EE36-0AA2?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1132-5EE36-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1132-5EE36-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}