{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1150-3EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1150-3EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1150-3EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1150-3EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1150-3EE32-0AA0, molded case circuit breaker, 3-pole, TM220 release, 50 A (40 °C), 76 kA at 240 V AC, 70 mm depth, IP40 front.","salesMarkdown":"Its TM220 thermal-magnetic release combines a thermal bimetal for overloads and a magnetic coil for short circuits — the 220 frame size indicates a 50 A continuous rating at 40 °C. That 50 A holds flat up to 50 °C; above that, the thermal curve derates to 49 A at 55 °C, 48 A at 60 °C, and 45 A at 70 °C. For a buyer sourcing this into a warm enclosure, the 70 °C derated value is the one that governs the real load. The interrupting ratings cover the common industrial voltage tiers: 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V. That 53 kA at 415 V is the figure that matters for most European and Asian 400 V-class panels — it determines whether this breaker coordinates with upstream gear or needs a current-limiting device ahead of it. Dimensions: 70 mm deep, 76.2 mm wide, 130 mm tall. The 76.2 mm width (3 inches) is a standard 3-pole MCCB footprint — it fits most DIN-rail or panel-mount enclosures without re-drilling.","metaTitle":"Siemens 3VM1150-3EE32-0AA0 MCCB, 50 A, 76 kA at 240 V","metaDescription":"Siemens SENTRON 3VM1150-3EE32-0AA0 molded case circuit breaker, 3-pole, 50 A rated at 40 °C, 76 kA breaking at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1150-3EE32-0AA0","Height":"130 mm","Maximum":"500 A","Minimum":"1 s","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"12 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM220, ATFM, In=50A overload protection Ir=35A...50A short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"15 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0242732df17f34003fb92c633b30615a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575062&mlfb=3VM1150-3EE32-0AA0"},"ai":{"faq":[{"question":"What are the key ratings of 3VM1150-3EE32-0AA0?","answer":"50 A continuous at 40 °C, derating to 45 A at 70 °C; interrupting capacity 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, 12 kA at 500 V; 3-pole; TM220 release; 70 mm depth; IP40 front."},{"question":"Where can I buy 3VM1150-3EE32-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation is available for 3VM1150-3EE32-0AA0?","answer":"As a Siemens SENTRON MCCB, it carries the standard industrial certifications — UL, CSA, CE, and IEC 60947-2 compliance is typical for the series. Specific declarations (RoHS, REACH) are available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1150-3EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1150-3EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}