{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1163-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1163-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1163-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1163-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VM1163-3ED22-0AA0, 2-pole molded case circuit breaker, 63 A, TM210 thermal-magnetic trip, 76 kA at 240 VAC, 53 kA at 415 VAC.","salesMarkdown":"The SENTRON 3VM1163-3ED22-0AA0 is a 2-pole molded case circuit breaker (MCCB) from the 3VM series, designed for line protection in distribution panels. It carries a TM210 thermal-magnetic trip unit rated at 63 A continuous current, with a fixed thermal element and magnetic instantaneous pickup set at 10× In (630 A). The 63 A rating is sustained up to 50 °C ambient; above that it derates linearly to 58 A at 70 °C, so in a warm enclosure you need to account for the thermal curve rather than the nameplate. Breaking capacity is 76 kA at 240 VAC and 53 kA at 415 VAC — these are the maximum fault currents the breaker can safely interrupt at those voltages without welding contacts or rupturing. For DC systems, the manual (3VA Molded Case Circuit Breaker Manual) provides the specific switching capacity values; the breaker is rated for 250 VDC operation. The 2-pole configuration (50.8 mm wide, 130 mm tall, 70 mm deep) fits standard DIN-rail or panel-mount layouts. ## Integration and wiring considerations If you need remote tripping or ground-fault indication, you are looking at a different variant in the 3VM family. Maximum power loss is 12 W at rated current. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C.","metaTitle":"SENTRON 3VM1163-3ED22-0AA0 MCCB, 63 A, 2-Pole, TM210, 76 kA","metaDescription":"SENTRON 3VM1163-3ED22-0AA0 molded case circuit breaker, 63 A, 2-pole, TM210 thermal-magnetic trip, 76 kA at 240 VAC, 53 kA at 415 VAC. Currently in active production. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"630 A","Minimum":"1 s","at 240 V":"76 kA","at 415 V":"53 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/062f3aac021d2a63afaa57f8f1129f30.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575083&mlfb=3VM1163-3ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1163-3ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VM1163-3ED22-0AA0 include an undervoltage release or shunt trip?","answer":"No. This variant has no undervoltage release, no shunt trip, no communication function, and no ground-fault monitoring. It is a bare thermal-magnetic breaker for line protection only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1163-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1163-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}