{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1163-3ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1163-3ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1163-3ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1163-3ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VM1163-3ED42-0AA0, 4-pole molded case circuit breaker, 63 A at 40 °C, 76 kA breaking capacity at 240 V, TM210 release.","salesMarkdown":"## Line protection MCCB with TM210 release Its TM210 thermal-magnetic release provides adjustable overload response up to 630 A and fixed short-circuit protection — a common choice for feeder and distribution panels where coordination studies set the trip curve. Continuous current holds at 63 A from 40 °C through 50 °C, then derates linearly to 58 A at 70 °C. That means the breaker delivers its full nameplate rating across typical panel ambient conditions without a sizing penalty. Breaking capacity reaches 76 kA at 240 V AC, 53 kA at 415 V, and 32 kA at 440 V. Dimensions are 101.6 mm wide, 130 mm tall, 70 mm deep, fitting standard MCCB panel cutouts and busbar spacing for 4-pole devices. ## Electrical ratings and application context Maximum power dissipation is 17 W — a factor for thermal management in densely packed enclosures. The TM210 release is field-adjustable for the long-time pickup (Ir) via the front dial, but short-time and instantaneous settings are fixed — a consideration when coordination with downstream breakers requires a selective trip band.","metaTitle":"SENTRON 3VM1163-3ED42-0AA0 MCCB, 63 A, 76 kA at 240 V","metaDescription":"SENTRON 3VM1163-3ED42-0AA0 molded case circuit breaker, 4-pole, 63 A continuous, 76 kA breaking at 240 V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","title":"3VM1163-3ED42-0AA0","Height":"130 mm","at 240 V":"76 kA","at 415 V":"53 kA","at 440 V":"32 kA","at 500 V":"12 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.8 in","Width [In]":"4 in","Height [In]":"5.1 in","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @ 415V 4-pole, line protection TM210, FTFM, In=63A overload protection Ir=63A, not adjustable short-circuit protection Ii=10 x In N conductor unprotected nut keeper kit","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"690 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"630 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/062f3aac021d2a63afaa57f8f1129f30.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575085&mlfb=3VM1163-3ED42-0AA0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VM1163-3ED42-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels — no automated price or lead-time figure is published here."},{"question":"What is the breaking capacity of 3VM1163-3ED42-0AA0 at 240 V?","answer":"76 kA at 240 V AC, derating to 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V."},{"question":"What is the continuous current rating of 3VM1163-3ED42-0AA0 at elevated temperatures?","answer":"63 A from 40 °C through 50 °C, then derated to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1163-3ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1163-3ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}