{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1163-4ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1163-4ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1163-4ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1163-4ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, Molded case circuit breaker, 3VM1163-4ED32-0AA0, 3-pole, 63 A, TM210 thermal-magnetic trip, 121 kA at 240 V AC.","salesMarkdown":"The breaking capacity climbs to 121 kA at 240 V AC and still holds 76 kA at 415 V AC, 53 kA at 440 V AC, and 12 kA at 500 V AC — numbers that tell you it can live upstream of a high-fault transformer or a big motor control center without needing a current-limiting fuse ahead of it. At 55 °C it drops to 62 A, at 60 °C to 61 A, at 65 °C to 60 A, and at 70 °C to 58 A. That's a gentle slope, so if your panel ambient runs 55 °C on a summer afternoon you still get 62 A continuous. The rated insulation voltage is 800 V, and the max operating voltage is 690 V AC or 500 V DC, which covers most 480/277 V and 600 V industrial systems in North America and 400 V in Europe. No trip indicator, no undervoltage release, no communication module — this is a basic thermal-magnetic breaker, not a smart or remotely-tripped unit.","metaTitle":"Siemens 3VM1163-4ED32-0AA0 SENTRON MCCB, 63 A, 3-Pole, 121 k","metaDescription":"Siemens SENTRON 3VM1163-4ED32-0AA0 molded case circuit breaker, 63 A, 3-pole, TM210 trip unit. Breaking capacity 121 kA at 240 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VM1163-4ED32-0AA0","Height":"130 mm","at 240 V":"121 kA","at 415 V":"76 kA","at 440 V":"53 kA","at 500 V":"12 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM210, FTFM, In=63A overload protection Ir=63A, not adjustable short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"630 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/062f3aac021d2a63afaa57f8f1129f30.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575092&mlfb=3VM1163-4ED32-0AA0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VM1163-4ED32-0AA0?","answer":"Submit an RFQ through this listing. We source through multiple distribution partners and confirm current price and lead time at quote time — no automated stock numbers here, just a real quote."},{"question":"What is 3VM1163-4ED32-0AA0's breaking capacity at different voltages?","answer":"At 240 V AC it's rated 121 kA, at 415 V AC it's 76 kA, at 440 V AC it's 53 kA, and at 500 V AC it's 12 kA. These are the maximum interrupting ratings for the TM210 trip unit at those voltages."},{"question":"What temperature range does this MCCB handle?","answer":"Operating range is -25 °C to +70 °C. Storage range is -40 °C to +80 °C. The 63 A rating derates above 50 °C — at 55 °C it's 62 A, at 70 °C it's 58 A."},{"question":"What compliance documentation does this brand provide for 3VM1163-4ED32-0AA0?","answer":"As a Siemens SENTRON MCCB, it carries IEC 60947-2 certification for molded case circuit breakers. The reference code per IEC 81346-2 is Q. Specific RoHS/REACH/UL documentation should be available from Siemens' technical support or the product manual."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1163-4ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1163-4ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}