{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1180-3ED12-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1180-3ED12-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1180-3ED12-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1180-3ED12-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1180-3ED12-0AA0, 1-pole molded case circuit breaker, 80 A, TM210 thermal-magnetic release, 53 kA at 240 V AC, 70 mm depth.","salesMarkdown":"## 1-pole MCCB for line protection — 80 A, 53 kA at 240 V The Siemens SENTRON 3VM1180-3ED12-0AA0 is a 1-pole molded case circuit breaker rated 80 A continuous at 40 °C, with a TM210 thermal-magnetic release (fixed Ir = 80 A, adjustable Ii = 800 A). It delivers 53 kA interrupting capacity at 240 V AC and 7.5 kA at 415 V AC, making it a fit for high-fault service-entrance or distribution panels where the upstream transformer can deliver heavy short-circuit current. Above that, it derates gradually: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. ## Mechanical fit and panel integration Power dissipation at rated load is 6.4 W, so factor that into the enclosure thermal budget.","metaTitle":"Siemens 3VM1180-3ED12-0AA0 SENTRON MCCB, 1-pole 80 A, 53 kA","metaDescription":"Siemens SENTRON 3VM1180-3ED12-0AA0 molded case circuit breaker, 1-pole, 80 A, 53 kA at 240 V AC, TM210 release, 70 mm depth. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","Height":"130 mm","at 240 V":"53 kA","at 415 V":"7.5 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.8 in","Width [In]":"1 in","Height [In]":"5.1 in","Number Of Poles":"1","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"6.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"80 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"125 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / lg min.":"80 A","Adjustable response value current / li max.":"800 A","Adjustable response value current / li min.":"800 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"415 V","Mechanical Service Life (Switching Cycles) / Typical":"12 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6,5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6b83f4d79e7ee56746fefe46987ce53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575151&mlfb=3VM1180-3ED12-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1180-3ED12-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VM1180-3ED12-0AA0?","answer":"Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the interrupting capacity of 3VM1180-3ED12-0AA0 at 240 V?","answer":"It is rated 53 kA at 240 V AC, and 7.5 kA at 415 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1180-3ED12-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1180-3ED12-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}