{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1180-3ED16-0AA2","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1180-3ED16-0AA2","canonicalUrl":"https://aoctrl.com/siemens/3VM1180-3ED16-0AA2","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1180-3ED16-0AA2","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1180-3ED16-0AA2, 1-pole molded case circuit breaker, 80 A, breaking capacity class N, 53 kA at 240 V, 7.5 kA at 415 V, TM210 release, LI protection, IP40 front, box terminal.","salesMarkdown":"Its LI protective function means it provides instantaneous short-circuit protection (Ii = 10 x In) plus fixed thermal overload protection (Ir = 80 A, not adjustable). Breaking capacity class N delivers 53 kA at 240 V AC and 7.5 kA at 415 V AC — enough for most commercial and light industrial panelboards where fault current stays under those thresholds. ## Thermal performance and derating Above that, derating kicks in: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. ## Integration and connections Main circuit connects via box terminals on the front face, accepting solid or stranded copper. Use inside a panel, not exposed to washdown.","metaTitle":"Siemens 3VM1180-3ED16-0AA2 MCCB, 1-pole, 80 A, 53 kA at 240","metaDescription":"Siemens SENTRON 3VM1180-3ED16-0AA2 molded case circuit breaker, 1-pole, 80 A, 53 kA at 240 V, 7.5 kA at 415 V, TM210 release, LI protection, IP40 front. Current lifecycle. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"title":"3VM1180-3ED16-0AA2","at 240 V":"53 kA","at 415 V":"7.5 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","description":"circuit breaker 3VM1 IEC frame 160 breaking capacity class N Icu=25kA @ 240V 1-pole, line protection TM210, FTFM, In=80A overload protection Ir=80A, not adjustable short-circuit protection Ii=10 x In terminal connection","Number of poles":"1","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"6.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"80 A","Rated insulation voltage Ui":"500 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM210","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product extension / optional / motor drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6b83f4d79e7ee56746fefe46987ce53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=682839&mlfb=3VM1180-3ED16-0AA2"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VM1180-3ED16-0AA2 at 240 V and 415 V?","answer":"At 240 V AC it's rated 53 kA; at 415 V AC it drops to 7.5 kA. The class N designation tells you it's optimized for the lower-voltage, higher-fault end."},{"question":"Can I buy 3VM1180-3ED16-0AA2 and what is the lead time?","answer":"This part is available to order against an RFQ through independent distribution. Current pricing and lead time are confirmed at quote time — no stock figures or ship dates are published here."},{"question":"Will 3VM1180-3ED16-0AA2 drop into a panel designed for 3VA1010-2ED32-0JA0?","answer":"No — the 3VA1010-2ED32-0JA0 is a 3-pole, 100 A frame breaker with different dimensions and terminal layout. The 3VM1 is a 1-pole, 160 A frame; they are not footprint-compatible without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1180-3ED16-0AA2","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1180-3ED16-0AA2 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}