{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1180-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1180-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1180-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1180-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1180-3ED22-0AA0, molded case circuit breaker, 2-pole, 80 A at 40 °C, 76 kA at 240 VAC, TM210 release, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VM1180-3ED22-0AA0 is a 2-pole molded case circuit breaker rated 80 A continuous at 40 °C through 50 °C, with a small derate to 74 A at 70 °C. That flat thermal curve means you can load it near its nameplate in a warm enclosure without recalculating every degree — useful when the panel sits next to a motor or drive. The TM210 thermal-magnetic release gives fixed time-current curves — no interchangeable trip units, but also no adjustment screw to drift out of spec on a hot afternoon. Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — a 2-inch wide footprint that fits a standard panel cutout. ## What the 3VA sibling changes — and when it matters The 3VA1010-2ED32-0JA0 is the electronic-trip sibling in the same SENTRON family. Both are 2-pole, 80 A MCCBs with the same physical footprint. The 3VM carries a TM210 thermal-magnetic release — fixed curve, no adjustments. The 3VA uses an electronic trip unit with adjustable I²t and short-time delay settings. If your coordination study calls for selective tripping or you need to dial in the curve for a generator feed, the 3VA is the right pick. For straightforward branch-circuit protection where you want a fixed, no-dial breaker that won't get re-calibrated by accident, the 3VM fits. The 50.8 mm width matches standard 2-pole MCCB spacing — no surprises when you lay out a multi-breaker panel. Line and load lugs accept copper or aluminum conductors; torque values are marked on the case. It's a plain-vanilla line-protection breaker — install it, torque it, label it, move on. The IP40 front keeps the handle and trip-indicator window clean in a typical industrial enclosure.","metaTitle":"Siemens 3VM1180-3ED22-0AA0 SENTRON MCCB, 80A 2-Pole, 76kA","metaDescription":"Siemens SENTRON 3VM1180-3ED22-0AA0 molded case circuit breaker, 80A rated at 40°C, 2-pole, 76 kA at 240 VAC. Active production. Quoted to order. RFQ for price and availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","at 240 V":"76 kA","at 415 V":"53 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Max. rated operational voltage Ue with DC":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Max. rated operational voltage Ue with AC 50/60Hz":"415 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6b83f4d79e7ee56746fefe46987ce53.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575152&mlfb=3VM1180-3ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1180-3ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VM1180-3ED22-0AA0 drop into a panel wired for 3VA1010-2ED32-0JA0?","answer":"Yes — same physical footprint, same pole count, same 80 A rating. The only functional difference is the trip technology. No rewiring needed if you're swapping between the two."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1180-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1180-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}