{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1196-4ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1196-4ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1196-4ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1196-4ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1196-4ED22-0AA0, molded case circuit breaker, 2-pole, 16 A, 76 kA at 415 V AC, TM210 release, IP40 front.","salesMarkdown":"## MCCB for line protection — 2-pole, 16 A continuous, 76 kA at 415 V The Siemens SENTRON 3VM1196-4ED22-0AA0 is a 2-pole molded case circuit breaker (MCCB) rated for line protection, carrying 16 A continuously from 40 °C up to 55 °C and derating to 15 A at 60–70 °C. The TM210 thermal-magnetic release is fixed, not adjustable, so the 16 A rating is the trip point; the instantaneous magnetic pickup li max is 320 A. Current production per lifecycle status. Storage range -40 to 80 °C; operating -25 to 70 °C. Maximum power loss 7 W.","metaTitle":"Siemens SENTRON 3VM1196-4ED22-0AA0 MCCB, 2-pole, 16 A, 76 kA","metaDescription":"Siemens SENTRON 3VM1196-4ED22-0AA0 molded case circuit breaker, 2-pole, 16 A (40-70 °C), 76 kA at 415 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"76 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Max. rated operational voltage Ue with DC":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Max. rated operational voltage Ue with AC 50/60Hz":"415 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7aa72781226d0a027871e875884a5cc5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=575182&mlfb=3VM1196-4ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1196-4ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VM1196-4ED22-0AA0 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is the interrupting capacity of 3VM1196-4ED22-0AA0?","answer":"121 kA at 240 V AC and 76 kA at 415 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1196-4ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1196-4ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}