{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1463-4ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1463-4ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1463-4ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1463-4ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON series, molded case circuit breaker, 3VM1463-4ED32-0AA0, 3-pole, 630 A at 40 °C, TM210 thermal-magnetic release, 121 kA breaking capacity at 240 V AC, line protection design.","salesMarkdown":"That rating holds flat through 50 °C — only above 55 °C does it begin to derate, reaching 583 A at 70 °C. Breaking capacity is specified per voltage: 121 kA at 240 V AC, 76 kA at 415 V and 440 V AC, and 53 kA at 500 V AC. At a typical 480 V industrial service, the interpolated value sits well above 50 kA — enough for most secondary distribution with transformer impedances under 6 %. No ground-fault monitoring or communication function is integrated; this is a straight thermal-magnetic breaker for conventional line protection. ## Peer comparison — 3VA1112-5EE32-0AA0 The closest functional peer within the SENTRON family is the 3VA1112-5EE32-0AA0. Both are 3-pole MCCBs with thermal-magnetic releases, but the 3VA1112 is a smaller-frame device rated for lower continuous current — typically 100–250 A range versus this part's 630 A. The 3VM1463-4ED32-0AA0 will not drop into a panel cutout designed for the 3VA1112 frame without busbar and mounting modifications; the footprint and lug spacing differ. Select the 3VM1463-4ED32-0AA0 when the load exceeds 300 A and the fault current at the service point demands the higher interrupting capacity.","metaTitle":"SENTRON 3VM1463-4ED32-0AA0 MCCB, 630 A, 3-Pole, TM210","metaDescription":"SENTRON 3VM1463-4ED32-0AA0 molded case circuit breaker, 630 A at 40 °C, 3-pole, TM210 release. Breaking capacity 121 kA at 240 V AC. Active production, sourced to order. Request qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","title":"3VM1463-4ED32-0AA0","Height":"248 mm","Maximum":"5 040 A","at 240 V":"121 kA","at 415 V":"76 kA","at 440 V":"76 kA","at 500 V":"53 kA","at 40 °C":"630 A","at 45 °C":"630 A","at 50 °C":"630 A","at 55 °C":"618 A","at 60 °C":"607 A","at 65 °C":"595 A","at 70 °C":"583 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","description":"circuit breaker 3VM1 IEC frame 630 breaking capacity class N Icu=36kA @ 415V 3-pole, line protection TM210, FTFM, In=630A overload protection Ir=630A, not adjustable short-circuit protection Ii=8 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"193 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7b5be2865836838c50d9901a75c69a7b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569141&mlfb=3VM1463-4ED32-0AA0"},"ai":{"faq":[{"question":"What is the depth of 3VM1463-4ED32-0AA0?","answer":"The depth is 110 mm (4.33 in), which fits standard switchboard and panelboard mounting arrangements."},{"question":"Will 3VM1463-4ED32-0AA0 drop into a panel specified around 3VA1112-5EE32-0AA0 without rewiring?","answer":"No. The 3VM1463-4ED32-0AA0 uses a larger frame with different busbar spacing and mounting hole pattern than the 3VA1112 series. Panel modifications and new buswork are required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1463-4ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1463-4ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}