{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VM1463-5ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VM1463-5ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VM1463-5ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VM1463-5ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VM1463-5ED42-0AA0, 4-pole molded case circuit breaker, rated 630 A at 40 °C, TM210 thermal-magnetic release, 187 kA at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VM1463-5ED42-0AA0 is a 4-pole molded case circuit breaker (MCCB) carrying a continuous current rating of 630 A at 40 °C, with the same rating held up through 50 °C. Above that it derates smoothly: 618 A at 55 °C, 607 A at 60 °C, 595 A at 65 °C, and 583 A at 70 °C. That thermal curve means you can push it into a warm enclosure without losing capacity until you cross 50 °C — a real advantage in a packed panel or near a motor drive. It's fitted with a TM210 thermal-magnetic trip unit — fixed thermal and magnetic settings, no electronic adjustment. The adjustable short-circuit pickup (li) maxes at 5 040 A, which gives some field flexibility for coordinating with downstream feeders. ## Breaking capacity — what it can interrupt The interrupting ratings span the common industrial voltages: 187 kA at 240 V AC, 121 kA at 415 V and 440 V AC, and 76 kA at 500 V AC. The product lifecycle status is listed as current production, so this isn't an obsolete or end-of-life part. For a BOM line that needs the 630 A 4-pole footprint with a TM210 release, this is the active catalog number.","metaTitle":"Siemens SENTRON 3VM1463-5ED42-0AA0 MCCB, 630 A, 4-Pole, TM21","metaDescription":"Siemens SENTRON 3VM1463-5ED42-0AA0 molded case circuit breaker, 630 A at 40 °C, 4-pole, TM210 release, 187 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"184 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"76 kA","at 40 °C":"630 A","at 45 °C":"630 A","at 50 °C":"630 A","at 55 °C":"618 A","at 60 °C":"607 A","at 65 °C":"595 A","at 70 °C":"583 A","Depth [In]":"4.3 in","Width [In]":"7.2 in","Height [In]":"9.8 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"193 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"690 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching capacity values in DC power systems, see the 3VA Molded Case Circuit Breaker Manual; link available under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"5 040 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Max. rated operational voltage Ue with AC 50/60Hz":"500 V","Mechanical Service Life (Switching Cycles) / Typical":"15 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7a9733c93aaa43bfbacf405a4c6132ef.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569148&mlfb=3VM1463-5ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VM1463-5ED42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VM1463-5ED42-0AA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VM1463-5ED42-0AA0's listed depth (110 mm) on this component line?","answer":"The depth is 110 mm (4.3 in), with a width of 184 mm (7.2 in) and height of 248 mm (9.8 in)."},{"question":"What compliance documentation does this brand provide for 3VM1463-5ED42-0AA0?","answer":"As a Siemens SENTRON MCCB, it carries the usual IEC 60947-2 compliance and UL/CSA listings typical for this class. Specific RoHS/REACH declarations are available from Siemens documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VM1463-5ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VM1463-5ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}