{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"47132","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"47132","canonicalUrl":"https://aoctrl.com/schneider/47132","factsUrl":"https://aoctrl.com/api/mcp/products/47132","rawCanonicalId":null},"summary":{"shortDescription":"Circuit breaker frame, MasterPact NT10L1, 1000A, 130kA/440VAC 50/60Hz (Icu), 3 poles, fixed, without control unit","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Range":"MasterPacT","Width":"276 mm","Height":"301 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact NT","Mounting mode":"Fixed","Sensor rating":"400 A 1000 A","Product weight":"14 kg","lifecycle_stage":"unknown","Connection pitch":"70 mm","Mounting support":"Backplate Rails","Performance type":"L1 130 kA 440 V AC","Pollution degree":"3 conforming to IEC 60664-1","Poles description":"3P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"1000 A at 40 °C","Downside connection":"Front Rear","Circuit breaker name":"MasterPact NT10L1","Selectivity category":"Category A","Electrical durability":"3000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 2000 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2","Maximum breaking time":"9 ms","Mechanical durability":"12500 cycles without maintenance","Power dissipation in W":"110 W","IP degree of protection":"IP30 conforming to IEC 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"50 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"10 kA 0.5 s","[Icm] rated short-circuit making capacity":"330 kA 220/415 V AC at 50/60 Hz 286 kA 440 V AC at 50/60 Hz 220 kA 525 V AC at 50/60 Hz 52 kA 690 V AC at 50/60 Hz","Integrated instantaneous protection (DIN in kA peak)":"9...11 kA","[Icu] rated ultimate short-circuit breaking capacity":"150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0030581d07f3782126210762950b5dad.pdf","sourceUrl":"https://www.se.com/vn/en/product/47132/circuit-breaker-frame-masterpact-nt10l1-1000a-130ka-440vac-50-60hz-icu-3-poles-fixed-without-control-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/47132/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/47132","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/47132 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}