{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"48499","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"48499","canonicalUrl":"https://aoctrl.com/schneider/48499","factsUrl":"https://aoctrl.com/api/mcp/products/48499","rawCanonicalId":null},"summary":{"shortDescription":"Control unit MicroLogic 5.0E, MasterPact NW drawout, selective protections (LSI), energy meter","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Range":"MasterPact","Display type":"Digital display","Network type":"AC","Thermal memory":"20 mn","Trip unit name":"MicroLogic 5.0 E","Number of poles":"4P 3P","Protection type":"for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection","lifecycle_stage":"unknown","Local signalling":"3 LEDs (red) for electrical fault 1 LED (red) for internal error","Range of product":"MasterPact NW","Trip unit rating":"800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C","Network frequency":"50/60 Hz","Device application":"Distribution","Type of measurement":"Energy meter","Trip unit technology":"Electronic","Communication of data":"Measurement readout Protection and alarm settings","Earth-leakage protection":"Without","Product or component type":"Control unit","Protected poles description":"4t 3t 3t + N/2","Circuit breaker mounting mode":"Drawout","Trip unit protection functions":"Selective protection","Zone selective interlocking ZSI":"With","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Adjustable 9 settings","Short-time protection delay adjustment type tsd":"Adjustable","[Tr] Long-Time Protection Delay Adjustment Range":"0.7...16.6 s at 7.2 x Ir 0.7...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","[tsd] Short-time protection delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"2...15 x In Off","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,599.61","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/258aeac4d89866555fe76c04915f4689.pdf","sourceUrl":"https://www.se.com/au/en/product/48499/control-unit-micrologic-5-0e-masterpact-nw-drawout-selective-protections-lsi-energy-meter/","alternativesUrl":"https://aoctrl.com/api/mcp/products/48499/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/48499","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/48499 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}