{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EM5107-7CB00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EM5107-7CB00","canonicalUrl":"https://aoctrl.com/siemens/4EM5107-7CB00","factsUrl":"https://aoctrl.com/api/mcp/products/4EM5107-7CB00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EM5107-7CB00 commutating choke for converter applications, 1-phase, 230V AC, 36A rated current (40A max), 0.7mH inductance, IP00, screw terminals.","salesMarkdown":"The Siemens 4EM5107-7CB00 is a single-phase commutating choke (line reactor) designed for converter front ends. The 36 A rated current (40 A max) sets the continuous thermal limit at 40 °C ambient. Push beyond that and the winding temperature rises above the Class B (130 °C) insulation limit per IEC 60085, shortening life. The 18 W coil loss plus 26 W iron core loss — 44 W total at rated load — must be dissipated in the enclosure; at IP00 (open-frame), forced airflow or at least 100 mm clearance to adjacent metal is the rule in a panel. The 0.7 mH inductance is sized for a 4 % voltage drop at rated current and 50 Hz — a common design target for commutating chokes in 6-pulse drives. That impedance limits the peak fault current during a shorted output device, but it also drops about 9 V at full load. Verify the converter's minimum DC-link voltage under load; a 230 V input with this choke still leaves roughly 221 V RMS before the rectifier, which is fine for most standard 230 V drives. ## Mounting and connection The 97 mm wide × 111 mm tall × 129 mm deep footprint is a standard open-frame choke — no DIN rail clip, no flange. It sits on a panel or sub-plate via its own mounting feet (not detailed in the spec, but typical for this Siemens series). Screw-type terminals accept the main circuit wiring; no auxiliary terminals for thermistor or fan control. IP00 means no housing, so it must live inside a clean, dry enclosure — not on the shop floor or in a washdown zone.","metaTitle":"Siemens 4EM5107-7CB00 Commutating Choke, 40A, 230V AC, 0.7mH","metaDescription":"Siemens 4EM5107-7CB00 commutating choke for converters. 1-phase, 230V AC, 36A rated (40A max), 0.7mH, IP00. Mature lifecycle; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"0.129 m","Width":"0.097 m","Height":"0.111 m","IP Rating":"IP00","Product Status":"Mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=380300&mlfb=4EM5107-7CB00","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EM5107-7CB00/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EM5107-7CB00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EM5107-7CB00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}