{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EP3600-3US00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EP3600-3US00","canonicalUrl":"https://aoctrl.com/siemens/4EP3600-3US00","factsUrl":"https://aoctrl.com/api/mcp/products/4EP3600-3US00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 4EP3600-3US00 mains choke for frequency converters, 3-phase, 500 V AC, 22.4 A, 0.82 mH, 50 Hz, IP00, screw terminals.","salesMarkdown":"The Siemens 4EP3600-3US00 is a three-phase mains choke (line reactor) designed for use with frequency converters — the German product designation \"Netzdrossel f. FU\" tells you exactly that. It's rated for 22.4 A maximum continuous current at 500 V AC, 50 Hz, with an inductance of 0.82 mH and a relative inductive voltage drop of 2% at rated conditions. That 2% drop is typical for a line reactor sized to smooth incoming power and limit harmonic distortion and peak currents on the drive's input side. The 22.4 A rating is the thermal maximum (Ithmax) — the continuous current it can carry at 40 °C ambient without exceeding the Class B temperature rise limit per IEC 60085. The slightly lower 20.16 A operational current (I LN) reflects the nominal load point under rated voltage and frequency. Total power loss splits between 49.6 W in the coil and 3.8 W in the iron core, which matters for enclosure heat buildup. Dimensions are 0.148 m wide by 0.139 m tall by 0.078 m deep, with screw-type terminals for the main circuit connections. Plan for adequate clearance around the choke for airflow; the 49.6 W coil loss needs ventilation to stay within the 40 °C ambient rating.","metaTitle":"Siemens 4EP3600-3US00 Mains Choke, 22.4 A, 0.82 mH, 500 V AC","metaDescription":"Siemens 4EP3600-3US00 3-phase mains choke for VFDs. Rated 22.4 A at 500 V AC, 0.82 mH, 50 Hz. IP00 open-frame, screw terminals. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.078m","Width":"0.148m","title":"4EP3600-3US00","Height":"0.139m","description":"MAINS CHOKE F.FU; PHASES:3; UN1(V):500; ITHMAX 1(A) / F1(HZ):22,4 /50; I LN (A):20,16; UK(%):2; LN(MH):0,82; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:SCREW CONNECTION; EN 61558-2-20 >UL/CSA-RECOGNIZED< >CHOKE<","Phase Number":"3","Type Of Voltage":"AC","lifecycle_stage":"mature","Product Designation":"Netzdrossel f. FU","protection class IP":"IP00","current at AC maximum":"22.4A","Inductivity Rated Value":"0.00082H","power loss [W] of the coil":"49.6W","Operating Voltage Rated Value":"500V","Ambient Temperature Rated Value":"40°C","Operating Frequency Rated Value":"50Hz","power loss [W] of the iron core":"3.8W","thermal class acc. to IEC 60085":"B","operational current at AC rated value":"20.16A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Relative Inductive Drop In Voltage For Rated Value Of The Current, Voltage And Frequency":"2%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/98a162c712369f9cd0e368e92de0d318.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=328935&mlfb=4EP3600-3US00"},"ai":{"faq":[{"question":"What compliance documentation does the 4EP3600-3US00 carry?","answer":"The part is UL/CSA-recognized and built to EN 61558-2-20, which covers reactors and chokes. It also carries the CE mark as a Siemens industrial product."},{"question":"Where can I buy 4EP3600-3US00 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current pricing and availability — quantities and lead times are confirmed at quote time."},{"question":"What are the key ratings for 4EP3600-3US00?","answer":"Rated 22.4 A maximum continuous current at 500 V AC, 50 Hz, with 0.82 mH inductance and a 2% voltage drop at rated load. Operational current is 20.16 A. Ambient rating is 40 °C with Class B insulation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EP3600-3US00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EP3600-3US00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}