{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"4EP3600-5US00","brand":"Siemens","brandSlug":"siemens","productSlug":"4EP3600-5US00","canonicalUrl":"https://aoctrl.com/siemens/4EP3600-5US00","factsUrl":"https://aoctrl.com/api/mcp/products/4EP3600-5US00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 4EP3600-5US00, 3-phase mains choke for VFD, 400/480V AC, 28A max, 0.5mH, 2% voltage drop, IP00, screw terminals.","salesMarkdown":"It filters harmonics and limits inrush current on the line side of the drive, rated for 400/480V AC at 50/60 Hz. The 0.5 mH inductance and 2% relative voltage drop are sized for a continuous operational current of 25.2 A, with a maximum thermal current of 28 A. This is an open-frame (IP00) component — no enclosure, so it mounts inside a panel or cabinet where the ambient temperature stays at or below 40°C. Screw terminals for the main circuit make for straightforward wiring with ring or fork lugs. 25.2 A continuous current at rated voltage and frequency. 28 A max thermal current for brief overloads. 2% voltage drop at rated current. Thermal class B per IEC 60085 means the insulation system is rated for a 130°C maximum hot-spot temperature. The 37.4 W copper loss plus 7.7 W iron core loss (45.1 W total) is the heat this choke dumps into the panel — plan ventilation or derating if the cabinet runs above 40°C. Mounts on the panel floor or a mounting plate — no DIN rail clip, so allow for screw-down lugs. Dimensions are 0.148 m wide, 0.139 m tall, 0.078 m deep. The IP00 rating means no touch protection; locate it where live terminals are not reachable during operation, or add a finger-safe shield. Wire it between the line supply and the drive input. The 2% voltage drop is consistent with typical drive reactor sizing; no need to adjust the drive's DC bus parameters for this value. Screw terminals accept standard ring lugs for the 25 A circuit. The 5SJ3140-7 and 5SQ2xxx peers in the evidence are miniature circuit breakers, not line reactors — they are not functional substitutes. No direct second-source exists for this specific choke; the 4EP3 series is Siemens' own line of drive input reactors.","metaTitle":"Siemens 4EP3600-5US00 Mains Choke for VFD, 3-Phase, 28A, 0.5","metaDescription":"Siemens 4EP3600-5US00 mains choke for VFD. 3-phase, 400/480V AC, 28A max, 0.5mH, 2% voltage drop. IP00, screw terminals. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Line/Load Reactors"],"specifications":{"Depth":"0.078m","Width":"0.148m","Height":"0.139m","Phase Number":"3","Type Of Voltage":"AC","lifecycle_stage":"mature","Product Designation":"Netzdrossel f. FU","protection class IP":"IP00","current at AC maximum":"28A","Inductivity Rated Value":"0.0005H","power loss [W] of the coil":"37.4W","Operating Voltage Rated Value":"400, 480V","Ambient Temperature Rated Value":"40°C","Operating Frequency Rated Value":"50 ... 60Hz","power loss [W] of the iron core":"7.7W","thermal class acc. to IEC 60085":"B","operational current at AC rated value":"25.2A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Relative Inductive Drop In Voltage For Rated Value Of The Current, Voltage And Frequency":"2%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b3bd88f34714318b62c7e60cadf88617.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=464589&mlfb=4EP3600-5US00","alternativesUrl":"https://aoctrl.com/api/mcp/products/4EP3600-5US00/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of 4EP3600-5US00?","answer":"Width 0.148 m, height 0.139 m, depth 0.078 m. Open-frame IP00, no DIN rail clip."},{"question":"What compliance documentation does Siemens provide for this choke?","answer":"The listing notes UL/CSA recognition and compliance with EN 61558-2-20. Standard Siemens documentation includes the CE declaration and the datasheet. RoHS and REACH declarations are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/4EP3600-5US00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/4EP3600-5US00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}